Chapter 5 Function parameter
46
code by user.
Panel potentiometer analog input voltage of 0V to 10V.
4: Analog AI1 + AI2 setting: refers to that the frequency is set by the analog input
terminals.
Note: when the analog AI1/AI2 is selected as 0 to 20mA input, the voltage
corresponding to 20mA is 10V
5: Multi-speed operation setting: when multi-speed operation setting mode is
selected, the inverter will run at multi-speed mode. Select current stage through setting
multi-speed terminal combinations of F1 group; determine the running frequency of
current stage through parameters of E1 group.
6: PID control setting: when PID control setting mode is selected, the inverter
will run at PID control mode. At this point, you need to set E2 group "PID function
group". The inverter's operation frequency is the frequency value after PID function is
applied. Where the meanings on PID given source, given quantity and feedback
source, etc. Please refer to the introduction of E2 group "PID function".
7: Remote communication setting: frequency command is set by the host
computer through the communication. For details, please refer to F9 group
communication protocol.
valid, and the inverter power
failure with data storage
0
valid, and the inverter power
failure without data storage
1
UP/DOWN setting invalid
2
F0.03 Keyboard and terminal
UP/DOWN setting
Valid when running, invalid
when stop
3
0
☆
Set the frequency through keyboard
▲
and
▼
keys and input terminals
UP/DOWN (frequency setting increment/frequency setting decrement) function, the
setting can be combined with other frequency setting channels. Notably tuning the
output frequency is required after completion of the commissioning process in the
control system
0: valid, and the inverter power failure with data storage You can set the
frequency command that the set frequency value is saved after the inverter with power
failure. the set frequency will restored to the frequency at the last power-down when
the inverter power-down and power-up again.
1: valid, and the inverter power failure without data storage You can set the
frequency command that the set frequency value is not saved after the inverter with
power failure.
2: UP/DOWN setting is invalid, keyboard
▲
and
▼
keys and input terminals
UP/DOWN function is invalid.
3: Set keyboard
▲
and
▼
keys and terminal UP/DOWN function setting as valid
when running, set keyboard
▲
and
▼
keys and input terminals UP/DOWN setting as
not save when stop.
Note: after user restores the default value of function parameters of the inverter,
the frequency value set by keyboard and input terminals UP/DOWN function is the
factory setting value.
Chapter 5 Function parameter
47
Keyboard command channel
0
Terminal command channel
1
F0.04 Command source
channel
Communication command
channel
2
0
★
Select inverter control command channel. Inverter control command include:
start, stop, forward, reverse, jog and fault reset,etc.
0: keyboard command channel; RUN, STOP/RESET keys on keyboard is used to
run commands
1: terminal command channel; multi-function input terminal forward, reverse,
forward jog and reverse jog, etc is used to run commands.
2: communication command channel; the host computer runs commands through
the communication method.
F0.05 Acceleration time 1
0.1 to 3600.0s
Depends on models
☆
F0.06 Deceleration time 1
0.1 to 3600.0s
Depends on models
☆
Acceleration time: refers to the time required that the inverter accelerates from
0Hz to maximum output frequency (F0.08) ;
Deceleration time: refers to the time required that the inverter decelerates from
maximum output frequency (F0.08) to 0Hz.
Actual deceleration time = preset acceleration and deceleration time × (set
frequency/maximum frequency)
Output
frequency
Maximum
frequency
Set
frequency
Actual acceleration time
Time(t)
The set acceleration time
Actual deceleration time
The set deceleration time
Acceleration and deceleration time schematic that the set frequency is less than
the maximum frequency.
CA SERIES inverter has two groups of deceleration time.
First group: F0.05, F0.06; second group: F7.03, F7.04
Acceleration and deceleration time can be selected by using the multi-function
input terminals (F1 group) . The fault value of acceleration and deceleration time is the
first group.
F0.07 Carrier frequency setting
1.0 to 15.0kHz
Depends on
models
☆
Summary of Contents for CA-203A
Page 1: ...Vector control inverter Operating manual CA Series www tpg tw com...
Page 61: ...1 TPG Corp TPG Corp 1 1 1 1 1 1 1 1 1 2 1 2...
Page 62: ...2 1 2 U V W EMC P RB R S T U V W 3 U V W AC36V 1 3 1 500V 5M 2 3 0Hz 400Hz 50Hz 4 5 PWM...
Page 70: ...18 4 7 CA Series K1 K1 K1 R S T MC1 MC2 MC1 MC2 M 3 4 5 19 4 8 4 6 R S T...
Page 101: ...80 7 1 3 7 3 81 8 1 6 LED OLED 2 1 R S T U V W IGBT 8 2...
Page 109: ...MODBUS 05H 06H 07H 08H EPPROM...