Chapter 5 Function parameter
62
F5.02 Switching low point frequency 0.00Hz to F5.05
5.00Hz
☆
F5.03 Speed loop proportional gain 2 0 to 100
15
☆
F5.04 Speed loop integral time 2
0.01 to 10.00s
1.00 s
☆
F5.05 Switching high point frequency
F5.02 to F0.08 (maximum
output frequency)
10.00Hz
☆
The above parameters apply only to the vector control mode. Below switching
frequency 1 (F5.02), speed loop PI parameters: F5.00 and F5.01. Above switching
frequency 2 (F5.05), speed loop PI parameters: F5.03 and F5.04. Between the two, PI
parameters are obtained by the linear changes of two sets of parameters, as shown
below:
By setting the proportional coefficient and integral time of speed regulator, you
can adjust the characteristics of speed loop dynamic response of vector control.
Increasing the proportional gain as well as decreasing integral time, which can
accelerate the speed loop dynamic response, but the too large proportional gain is or the
too small integration time easily cause system oscillation and too large overshoot. The
too small proportional gain also easily lead to the system steady-state oscillation, and
the speed static difference may exist.
Speed loop PI parameters are closely related to and the inertia of system, shall be
adjusted based on the default PI parameters especially for different load needs, in order
to meet the needs of a variety of occasions.
F5.06
VC slip compensation
coefficient
50% to 200%
100%
☆
Slip compensation coefficient is used to adjust the slip frequency of vector
control, improve the accuracy of system speed control, if the parameter is appropriately
adjusted, the speed static difference can be effectively suppressed.
F5.07 Torque upper limit setting
0.0 to 200.0% (rated
inverter current)
150.0%
☆
Set the inverter rated output current corresponding to 100.0%.
5-2-8.F6 Group - Keyboard and display group
F5.00
,
F5.01
PI
parameters
Frequency
command
F5.02
F5.05
F5.03
,
F5.04
Schematic diagram of PI parameters
Chapter 5 Function parameter
63
Code
Parameter name
Setting range
Factory
default
Change
Valid only for panel control 0
Valid for both panel control
and terminal control
1
Valid for both panel control
and communication control 2
F6.00
STOP/RESET key stop
function selection
Valid for all control modes
3
3
☆
As for fault reset, STOP/RESET key is valid at any situation.
F6.01
Running status display
parameters selection
0 to 0xFFFF
BIT0: Running frequency
BIT1: Set frequency
BIT2: Bus voltage
BIT3: Output voltage
BIT4: Output current
BIT5: Running speed
BIT6: Output power
BIT7: Output torque
BIT8: PID setting value
BIT9: PID feedback value
BIT10: Input terminal status
BIT11: Output terminal status
BIT12: Analog AI1 value
BIT13: Analog AI2 value
BIT14: Current stage of multi-
speed
BIT15: Torque set value
03FF
☆
Inverter in the running state, the parameters are shown by the F6.01 limit, that is, a
16 bit binary number, if one is 1, then the corresponding parameters can be run at the
time, through the SHIFT key to view. If the bit is 0, the corresponding parameter will
not be displayed. Set the function code F6.01, the binary number will be converted to
sixteen decimal, enter the function code.
Such as:
Choose to monitor load speed, the F6.01 should be set to fifteenth 1; choose to
monitor the AI1 voltage, the F6.01 should be set to ninth 1, and so on. The following
data is obtained by assuming that all relative positions are set to 1 at the request:
1
0
2
3
4
5
6
7
8
9
1 0
1 1
1 2
1 3
1 4
1 5
1
1
1
1
0
0
0
1
1
0
1
0
1
1
0
1
No.
numeri cal
val ue
Data were divided into four groups according to 4 bits:
No.
15-12
11-8
7-4
3-0
numerical value
0111
1010
0100
1111
Then the data is pressed down the table (binary sixteen binary value table) to
check the results for ox7A4F.
F6.02
Stop status display
parameters selection
1 to 0x3FF
BIT0: Set frequency
0FF
☆
Summary of Contents for CA-203A
Page 1: ...Vector control inverter Operating manual CA Series www tpg tw com...
Page 61: ...1 TPG Corp TPG Corp 1 1 1 1 1 1 1 1 1 2 1 2...
Page 62: ...2 1 2 U V W EMC P RB R S T U V W 3 U V W AC36V 1 3 1 500V 5M 2 3 0Hz 400Hz 50Hz 4 5 PWM...
Page 70: ...18 4 7 CA Series K1 K1 K1 R S T MC1 MC2 MC1 MC2 M 3 4 5 19 4 8 4 6 R S T...
Page 101: ...80 7 1 3 7 3 81 8 1 6 LED OLED 2 1 R S T U V W IGBT 8 2...
Page 109: ...MODBUS 05H 06H 07H 08H EPPROM...