Chapter 5 Function parameter
36
7: even parity (E, 7, 1) for ASCII
8: odd parity (O, 7, 1) for ASCII
9: no parity (N, 7, 2) for ASCII
10: even parity (E, 7, 2) for ASCII
11: odd parity (O, 7, 2) for ASCII
12: no parity (N, 8, 1) for ASCII
13: even parity (E, 8, 1) for ASCII
14: odd parity (O, 8, 1) for ASCII
15: no parity (N, 8, 2) for ASCII
16: even parity (E, 8, 2) for ASCII
17: odd parity (O, 8, 2) for ASCII
137. F9.02
Communication
address of this unit
1 to 247, 0 for broadcast address
1
☆
138. F9.03
Communication
response delay
0 to 200ms
5ms
☆
139. F9.04
Communication
timeout fault time
0.0 (Invalid
)
;
0.1 to 100.0s
0.0 s
☆
140. F9.05
Data transfer
format selection
0: non-standard MODBUS
protocol
1: standard MODBUS protocol
2: ASCII
0
☆
141. F9.06
Transmission error
handling
0: Alarm and free stop
1: No alarm and continue to run
2: No alarm and stop at the
selected mode (under
communication control mode
only)
3: No alarm and stop at the
selected mode (under all control
modes)
1
☆
142. F9.07
Transmission
response handling
0: Write operations responded
1: Write operations not responded
0
☆
5-1-12.FA Group - Torque control
No. Code Parameter name
Setting range
Factory
default
Change
143. FA.00
Torque setting
mode selection
0: Keyboard setting (FA.01)
1: Analog AI1 setting
2: Analog AI2 setting
3: Panel potentiometer setting
4: Analog AI1+AI2 setting
5: Multi-segment torque setting
6: Remote communications
0
☆
Chapter 5 Function parameter
37
setting
Note: Option 1 to 6, 100%
relative to two times of the rated
current of inverter
144. FA.01
Keyboard set
torque
-200.0% to 200.0% (rated current
of inverter)
50.0%
☆
145. FA.02
low speed torque
compensation
0.000-1.000
0.050
☆
146. FA.03
high speed torque
compensation
0.000-1.000
0.000
☆
5-1-13.Fb Group - Control optimization
No. Code
Parameter name
Setting range
Factory
default
Change
147. Fb.00 Software overcurrent point
0 to 2000A
Depends on
models
★
148. Fb.01 Software undervoltage point
0 to 500V
Depends on
models
★
149. Fb.02 Software overvoltage point
300 to 800V
Depends on
models
★
150. Fb.03
Low-frequency threshold point of
oscillation suppression
0 to 500
5
☆
151. Fb.04
High-frequency threshold point of
oscillation suppression
0 to 500
100
☆
152. Fb.05
Amplitude limit value of
oscillation suppression
0 to 10000
5000
☆
153. Fb.06
Demarcation frequency of high and
low frequency of oscillation
suppression
0.00Hz to F0.08
(maximum
output
frequency)
12.50Hz
☆
154. Fb.07 Oscillation suppression
0: valid 1: invalid
1
☆
155. Fb.08 PWM selection
0: PWM mode 1
1: PWM mode 2
2: PWM mode 3
0
★
156. Fb.09 Energy-saving selection
0: OFF
1. Auto
0
★
157. Fb.10 Deadband time
2 to 5
Depends on
models
★
Summary of Contents for CA-203A
Page 1: ...Vector control inverter Operating manual CA Series www tpg tw com...
Page 61: ...1 TPG Corp TPG Corp 1 1 1 1 1 1 1 1 1 2 1 2...
Page 62: ...2 1 2 U V W EMC P RB R S T U V W 3 U V W AC36V 1 3 1 500V 5M 2 3 0Hz 400Hz 50Hz 4 5 PWM...
Page 70: ...18 4 7 CA Series K1 K1 K1 R S T MC1 MC2 MC1 MC2 M 3 4 5 19 4 8 4 6 R S T...
Page 101: ...80 7 1 3 7 3 81 8 1 6 LED OLED 2 1 R S T U V W IGBT 8 2...
Page 109: ...MODBUS 05H 06H 07H 08H EPPROM...