Faults with fault messages
Troubleshooting
• The system shows the detected errors by means of an error number. (e.g. error number 7).
• The control switches to message mode.
• When in operating mode the last error number can be displayed by pressing the button P.
Error number
Possible cause
Troubleshooting
7
120 seconds after the last key function the pro-
gramming mode terminates automatically.
• Start the programming procedure again.
9
No speed sensor impulse, system gets blocked.
• Get the drive system checked.
10
Door blocked / difficult to move.
• Remove the obstacle / keep the door balanced.
Maximum driving power setting too low.
• Maximum driving power has to be checked by
an specialized dealer.
„Level 2, Menu 1 -
Required driving force OPEN“
„Level 2, Menu 2 -
Required driving force CLOSE“
11
Running time limit.
• Get the drive system checked.
13
Safety edge triggered.
• Check the closing edge protective device.
15
Photocell triggered or defective..
• Remove the obstacle or check the photocell.
Photocell programmed but not connected.
• Deactivate or connect the photocell.
16
Current sensor for the automatic switchhoff
defective.
• Get the motor unit checked.
26
Undervoltage. System overloaded -
by setting the driving force at level 16 (maxi-
mum).
• Get the external power supply checked.
28
Door blocked / difficult to move or irregular
movement.
• Check the gate movement / remove the obstacle
/ keep the door balanced.
Automatic switch-off too sensitive.
•
Automatic switch-off has to be checked by an
specialized dealer.
„Level 2, Menu 3 -
Automatic switch-off OPEN“
„Level 2, Menu 4 -
Automatic switch-off CLOSE“
30
Error MS-Bus.
• Perform reset of the bus modules.
„Level 1, Menu 8 - RESET“
• Get the connected BUS modules checked.
33
Overtemperature due to overheating.
• Let the system cool down.
35
Electronics defective.
• Get the drive system checked.
36
Jumper removed, but stop button not connected.
• Insert the stop button or jumper plug.
„4.3 control connections“
Closing edge module disconnected.
• Check the closing edge module
48
Door blocked / difficult to move or irregular
movement.
• Check the door movement und Tor gangbar
machen.
Wrong setting for door position CLOSE.
• Check the door positions OPEN and CLOSE /
reset them.
• Check the door.