E6582175
17
■
Parameters changed default setting values
Table 1 : Parameter list changed default setting values at software V120 or later version
Title
Com.
No
Function
Unit
Minimum
setting unit
Panel/Com.
Adjustment
range
Default
setting
Reference
*2
vb
0016
Torque boost value 1
%
0.1 / 0.1
0.0 - 30.0
*1
6.4
f172
0172
Torque boost value 2
%
0.1 / 0.1
0.0 - 30.0
*1
6.8.1
f402
0402
Automatic torque boost value
%
0.1 / 0.1
0.1 - 30.0
*1
6.25
f415
0415
Motor rated current
A
0.01 / 0.01
0.10 - 100.00
*1
f416
0416
Motor no-load current
%
1 / 1
10 - 90
*1
f417
0417
Motor rated speed
min
-1
1 / 1
100 - 64000
*1
f456
0456
Motor specific constant 12
-
1 / 1
20 - 150
120
-
f457
0457
Motor specific constant 13
-
1 / 1
5 - 75
50
-
f458
0458
Motor specific constant 2
-
1 / 1
0 - 101
101
-
f459
0459
Load inertia moment ratio
Times
0.1 / 0.1
0.1 - 100.0
1.5
6.25
*1: Default setting values are different depending on the inverter ratings. (Refer to Table 3.)
*2: Refer to section 11.2 to 11.5.
■
Default setting, region setting
Regarding the change of the parameter default setting values described on Table 1, the several functions described below are
changed from V120 or later version.
Table 2 : Function changed at V120 or later version inverter
Item
Before (V116 or earlier version)
After (V120 or later version)
Reference
50Hz default setting
(
typ
=
1
)
Function is not changed.
f417
(Motor rated speed): 1410(min
-1
) is set. It is NOT dependent on the inverter ratings.
4.3.2
60Hz default setting
(
typ
=
2
)
Function is not changed.
f417
(Motor rated speed): 1710(min
-1
) is set. It is NOT dependent on the inverter ratings.
Default setting 1
(
typ
=
3
)
Parameters on Table 1 are initialized to the
values described on Table 4.
Parameters on Table1 are initialized to the
values described on Table 3.
Default setting 2
(
typ
=
13
)
Parameters on Table 1 are initialized to the
values described on Table 4.
(Region setting is required in advance)
Parameters on Table 1 are initialized to the
values described on Table 3.
(Region setting is required in advance)
Region setting
(
set
)
Parameters on Table 1 are initialized to the
values described on Table 4.
Parameters on Table 1 are initialized to the
values described on Table 3.
4.4
11.5
(
f456
and
f457
do not exist on V110 or earlier version inverter.)