3.
System Configuration Unit and Module
109
Diagnostic functions
1) Counter stop diagnostics
2) ROM/RAM check; WDT supervision; and power supply supervision
3) I/O bus transmission diagnostics
4) Duplex switching status diagnostics
5) External power supply voltage drop detection
*1 Among pulse inputs, it is possible to detect failures of the insulation and input areas
(each CH independent) by comparing the primary and secondary count values
when redundant. The errors at this time, which are displayed as input deviation
errors (AIE), are issued to both modules of the redundant configuration.
Examples of how failed modules are specified.
* Secondary-module error when the control is not affected
* Primary-module error when the control is affected
If diagnosing this part is necessary when single, the need can be handled via
software by entering parallel inputs into two modules.
*2 Panel SW and status display are not targeted for diagnosis. By conducting power
ON/OFF tests during routine maintenance, it is possible to check the
absence/presence of failures of panel switches and the lamp indication statuses of
panel LEDs.
*3 Some consistency errors may not be detected due to the timing of the diagnosis
cycle, etc.
SPI06 module external wiring
When mounted on UTBA1
+
24 Vdc
FG
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
FG
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
+
-
+
GND
(TB1/TB2)
GND
24 Vdc
(TB1/TB2)
Pulse
generator
(24 Vdc)
(0 V)
FG
PI1 (+)
PI1 ( - )
PI2 (+)
PI2 ( - )
PI3 (+)
PI3 ( - )
PI4 (+)
PI4 ( - )
SPI06
(24 Vdc)
(0 V)
(24 Vdc)
(0 V)
FG
PI1 (+)
PI1 ( - )
PI2 (+)
PI2 ( - )
PI3 (+)
PI3 ( - )
PI4 (+)
PI4 ( - )
SPI06
(24 Vdc)
(0 V)
GND
Pulse
generator
A ground bar (FSBR2) is used for shielding.
( - ) side internal connection.
( - ) side internal connection.
Summary of Contents for TOSDIC-CIE DS
Page 1: ...Toshiba Integrated Control System Intelligent PI O Instruction Manual 6F8C0779 ...
Page 10: ...Introduction viii ...
Page 14: ...Contents xii ...
Page 20: ...1 System Configuration 6 ...
Page 40: ...2 Installation and Wiring 26 ...
Page 53: ...3 System Configuration Unit and Module 39 UTBA1 front panel ...
Page 56: ...3 System Configuration Unit and Module 42 UTBA2 front panel ...
Page 59: ...3 System Configuration Unit and Module 45 UTBA3 front panel ...
Page 68: ...3 System Configuration Unit and Module 54 UTBD1 front panel ...
Page 71: ...3 System Configuration Unit and Module 57 UTRC1 front panel ...
Page 142: ......
Page 151: ...Apendix 2 External Dimentions 137 Terminal Block Unit Appended Figure 2 2 Terminal block unit ...
Page 156: ......
Page 158: ...TOSHIBA CORPRATION 72 34 Horikawacho Saiwai ku Kawasaki shi Kanagawa 212 8585 JAPAN ...