3.
System Configuration Unit and Module
115
Distributor Module SDA01
SDA01 module specifications
Item
Specification
Model name
SDA01
Sensor power supply output
8 points
Insulation
None
Sensor current limit
21 to 35 mA/point
Sensor power supply voltage drop 3.5 V or less with respect to input power supply (when sensor
current is 21 mA)
Output protection conditions
(1) sensor short up to 4 points simultaneously (continuous rating)
(2) output short to ground up to 1 point (continuous rating)
Alarm conditions
(1) during sensor current limit action
(2) input power supply cutoff
Alarm output
(1) alarm contact (rating 24 Vdc-100 mA, b contact)
(2) alarm indicator (effective except when input power supply is cut
OFF).
Sensor power supply switch
For each side
Insulation resistance
100 M
or more (measured with 500 Vdc megger, between alarm
contact and power supply circuit)
Ability of insulation to withstand
voltage
500 Vac for 1 minute (between alarm contact and power supply
circuit)
External power supply
24 Vdc
10%-180 mA (all-sensor current 20 mA), UTBA3 external
power supply
System power supply current
consumption
-
Internal heat generation
1 W or less (without current limiter action)
Compatible terminal block unit
UTBA3 (can be mounted on lower level)
Compatible I/O module
SAI01 (mounted on upper level of UTBA3)
Compatible options
FIVC11, FIVC12 (mounted on OP1 side)
External dimensions
40 W
90 H
95 D mm (excluding protrusions)
Weight
300 g or less
Summary of Contents for TOSDIC-CIE DS
Page 1: ...Toshiba Integrated Control System Intelligent PI O Instruction Manual 6F8C0779 ...
Page 10: ...Introduction viii ...
Page 14: ...Contents xii ...
Page 20: ...1 System Configuration 6 ...
Page 40: ...2 Installation and Wiring 26 ...
Page 53: ...3 System Configuration Unit and Module 39 UTBA1 front panel ...
Page 56: ...3 System Configuration Unit and Module 42 UTBA2 front panel ...
Page 59: ...3 System Configuration Unit and Module 45 UTBA3 front panel ...
Page 68: ...3 System Configuration Unit and Module 54 UTBD1 front panel ...
Page 71: ...3 System Configuration Unit and Module 57 UTRC1 front panel ...
Page 142: ......
Page 151: ...Apendix 2 External Dimentions 137 Terminal Block Unit Appended Figure 2 2 Terminal block unit ...
Page 156: ......
Page 158: ...TOSHIBA CORPRATION 72 34 Horikawacho Saiwai ku Kawasaki shi Kanagawa 212 8585 JAPAN ...