1. System Configuration
3
Standard System Expansion Configuration
As shown in Figure 1.2, the standard intelligent PI/O system consists of communication base
units connected or I/O base units connected with interconnectors to an PCS-DS serial bus, and
terminal block units connected to the communication base units via an I/O bus cable.
From the point of view of hardware the following is the composition of the maximum possible
system.
Table 1.1 Hardware composition of maximum possible system
Hardware
System element(s)
Number of communication
base units
Maximum 15
Number of PI/O modules
Maximum 14 (for single configuration)
Maximum 28 (for dualized configuration)
(Up to 14 terminal block units and I/O base units)
Serial bus
The SBIF1 and SBIF2 can be connected together on
the same serial bus.
Serial bus cables
Total length within 30 m
I/O bus
Only the dual SBIF2 modules (SAI06, SAO06) can
be connected. No other modules (SAI01, SAO01,
etc.) can be connected.
I/O bus cables
Overall length within 5 m including the lengths of
terminal block units and I/O base units.
I/O bus power supply
capacity
Within 2.2 A (per communication base unit)
When the power capacity is exceeded, connect a
power relay I/O bus cable (ZCS008A***1) between
terminal blocks or a UITU5 (I/O terminal unit) to the
final stage of the system.
Summary of Contents for TOSDIC-CIE DS
Page 1: ...Toshiba Integrated Control System Intelligent PI O Instruction Manual 6F8C0779 ...
Page 10: ...Introduction viii ...
Page 14: ...Contents xii ...
Page 20: ...1 System Configuration 6 ...
Page 40: ...2 Installation and Wiring 26 ...
Page 53: ...3 System Configuration Unit and Module 39 UTBA1 front panel ...
Page 56: ...3 System Configuration Unit and Module 42 UTBA2 front panel ...
Page 59: ...3 System Configuration Unit and Module 45 UTBA3 front panel ...
Page 68: ...3 System Configuration Unit and Module 54 UTBD1 front panel ...
Page 71: ...3 System Configuration Unit and Module 57 UTRC1 front panel ...
Page 142: ......
Page 151: ...Apendix 2 External Dimentions 137 Terminal Block Unit Appended Figure 2 2 Terminal block unit ...
Page 156: ......
Page 158: ...TOSHIBA CORPRATION 72 34 Horikawacho Saiwai ku Kawasaki shi Kanagawa 212 8585 JAPAN ...