3. System Configuration Unit and Module
71
Analog Input Module SAI02
SAI02 module specifications
Item Specification
Model name
SAI02
Number of input points
4 points
Input insulation unit
Each point is isolated separately.
Input signal level
1-5 Vdc
Maximum applied voltage
30 V peak
Input impedance
1 M
or more
Data updating period
18 ms
A/D conversion data
+6400 to +32000 counts
CMRR
100 dB or more (100 Vac-50/60 Hz)
Standard input accuracy
Within
.1% of full scale
Temperature drift
Within
0.015%/
C
Power supply voltage drift
0.1% of full scale (in a system with power supply fluctuation
of
10%)
Input wire break characteristics
Down scale
Input wire break detection time
Within 10 seconds
Address setting
Set from 1 to E (decimal 1 to 14) by front panel address setting
switch.
Diagnosis of breakdown
Analog standard voltage, transmission, CPU, memory
Insulation resistance
100M
or more (measured with 500 Vdc megger, between
input channels, between total inputs and internal circuits)
Ability of insulation to withstand
voltage
500 Vac for 1 minute (between input channels, between total
inputs and internal circuits)
Current consumption
24 Vdc-60 mA or less (system power supply)
Internal heat generated
1.5 W or less (rated condition)
Compatible terminal block unit
UTBA2
Compatible options
FIVC21, FIVC22
External dimensions
40 W
90 H
95 D mm (excluding protrusions)
Weight
150 g or less
Summary of Contents for TOSDIC-CIE DS
Page 1: ...Toshiba Integrated Control System Intelligent PI O Instruction Manual 6F8C0779 ...
Page 10: ...Introduction viii ...
Page 14: ...Contents xii ...
Page 20: ...1 System Configuration 6 ...
Page 40: ...2 Installation and Wiring 26 ...
Page 53: ...3 System Configuration Unit and Module 39 UTBA1 front panel ...
Page 56: ...3 System Configuration Unit and Module 42 UTBA2 front panel ...
Page 59: ...3 System Configuration Unit and Module 45 UTBA3 front panel ...
Page 68: ...3 System Configuration Unit and Module 54 UTBD1 front panel ...
Page 71: ...3 System Configuration Unit and Module 57 UTRC1 front panel ...
Page 142: ......
Page 151: ...Apendix 2 External Dimentions 137 Terminal Block Unit Appended Figure 2 2 Terminal block unit ...
Page 156: ......
Page 158: ...TOSHIBA CORPRATION 72 34 Horikawacho Saiwai ku Kawasaki shi Kanagawa 212 8585 JAPAN ...