30
TOSHIBA
The drive has various functions for setting the environment to ensure trouble-free operation.
These functions can be selected in two ways, automatic selection by the drive, and manual selection.
Setting the Environmental Functions (Maximum Frequency, Upper and Lower Limits, Base
Frequency, Etc.
Applicable parameters: Automatic environment setting
AU3
AU3
, upper limit frequency
UL
UL
,
maximum frequency
FH
FH
, lower limit frequency
LL
LL
, and base frequency
uL
uL
, (VIA/II input
point 2 frequency
F204
F204
, auto-restart
F30I
F30I
, regeneration power ride-through control
F302
F302
,
pattern of acceleration and deceleration
F502
F502
, output voltage adjustment
F306
F306
, power
voltage compensation
F307
F307
, and VIB point 2 frequency
F2I3
F2I3
)
Output frequency
50 Hz operation
100%
0%
0.0Hz
50Hz 60Hz
typ2
typ1
ub1
Ul
ll
60 Hz operation
Output voltage
Output frequency
Output frequency
*
*
100%
100%
* Maximum frequency
**
***
** Maximum frequency
*** Maximum frequency
% Voltage
% Voltage
Notes:
1) The 'Quick Setup Function' sets the motor speed lower than the frequency command in case of
an instantaneous power failure. If this has an adverse effect on the machine, change it by setting
manually.
Quick Setup Parameters
The set values differ with the source voltage rating of the motor as shown below:
50 Hz motor: Set
AU3
AU3
to 1.
60 Hz motor: Set
AU3
AU3
to 2.
C A U T I O N
Select a suitable source voltage for the motor. Improper voltage selection
could result in rotation failure or, in the worst case, the motor could be
damaged.
The automatic environment settings are as shown on page 31.