Technical Information

Replacement of the ZETADYN 3C frequency inverter with the ZAdyn4C frequency
inverter

Safety instructions

Danger!

It is forbidden to carry out work on electrically live parts.
In frequency inverters of the ZAdyn type, the intermediate circuit (terminals ZK+ / ZK- or +DC / -DC) are 
still under voltage even after switching off.

You must wait at least three minutes.

Danger!

It is not permitted to operate the frequency inverter with the housing covers removed, as exposed live 
parts are present inside the device. Failure to observe this provision can lead to serious injury.

Work on electric components may only be carried out by trained electricians or by persons instructed in 
electricity under the supervision of an electrician in accordance with electrical engineering regulations.

A second person must always be present when working on energized parts or lines who disconnects in 
case of emergency.

Electrical equipment must be checked regularly: Loose connections must be 

xed, damaged lines or 

cables must be replaced immediately. The switch cabinet and all electrical supply units must always be 
kept closed. Access is only allowed to authorised persons with a key or special tool.

Dimensioning of the frame size

CAUTION!

Caution!

The frame size of the ZAdyn4C frequency inverter must be dimensioned according to the nominal motor 
current.
In general, valid is:

I

Nenn Frequenzumrichter

 ≥

 I

Nenn Motor

Dimensions / Minimum distances

ZAdyn4C 011-032

ZD4C01M0

Dimensions  011-032 in mm

R-TIA14_12-GB 1528

Part.-No. 

english

Summary of Contents for ZETADYN 3C

Page 1: ...r by persons instructed in electricity under the supervision of an electrician in accordance with electrical engineering regulations A second person must always be present when working on energized pa...

Page 2: ...ZD4C01M0 Minimum clearances 011 032 in mm ZAdyn4C 040 074 ZD4C02M0 Dimensions 040 074 in mm ZD4C02M0 Minimum clearances 040 074 in mm Technische Information R TIA14_12 GB 1528 Part No 2 22...

Page 3: ...on the memory card and use it to load them onto the ZAdyn4C Pecedure for saving the parameters on the memory card Insert the memory card in the X MMC card slot on the controller unit see gure Memory...

Page 4: ...arge yourself by suitable action before working on electrical components connectors etc You can do this for example by touching earthed metal parts Information If the ZETADYN 3C is replaced by the ZAd...

Page 5: ...onnection ZETADYN 3C X2 ZAdyn4C X3 2 2 Connection terminal X2 ZETADYN 3C 2 2 Connection terminal X3 ZAdyn4C 011 032 2 2 Connection terminal X3 ZAdyn4C 040 074 ZETADYN 3C ZAdyn4C 2 Motor connection X2...

Page 6: ...ure monitoring of the motor X MT Temperature monitoring of the motor X MT P1 P1 P1 P1 P2 P2 P2 P2 Connection terminal X MT ZETADYN 3C Connection terminal X MT ZAdyn4C 011 032 Connection terminal X MT...

Page 7: ...X2 ZETADYN 3C 3 3 Connection terminal X2 ZAdyn4C 011 032 3 3 Connection terminal X2 ZAdyn4C 040 074 ZETADYN 3C ZAdyn4C 2 Brake chopper brake resistor X 2 Brake chopper brake resistor X 2 DC DC R R PE...

Page 8: ...ON ZAdyn4C Digital inputs X IN The connection assignment is identical on both ZETADYN 3C and ZAdyn4C The connecting lead can be reconnected directly from the ZETADYN 3C to the ZAdyn4C The connector on...

Page 9: ...OUT Article no 00165935 xxM ZETADYN 3C ZAdyn4C 2 Digital outputs X OUT Digital outputs X OUT O11 O14 fault 1 2 O11 O14 fault 1 2 O21 O24 MB brake 4 5 O21 O24 MB brake 3 4 O31 O34 RB contactor 7 8 O31...

Page 10: ...Encoder connection asynchronous mo tors X ENC8 Encoder connection asynchronous mo tors X ENC8 A A A 8 A A A 7 B B B 6 B B B 5 5 8V_E 5V 5V_E 4 GND GND GND 3 1 Connection terminal X ENC8 ZETADYN 3C TT...

Page 11: ...asynchronous motors ZETADYN 3C X ENC9 ZAdyn4C X ENC15 Use the adapter D SUB 9 D SUB 15 when connecting the encoder cable to the connection terminal X ENC15 of the ZAdyn4C Type designation of the adapt...

Page 12: ...replaced with the encoder cable L GL 10 YY ZA4 ERN1387 article no 00165948 10M DCP Schnittstelle X DCP The connection assignment is identical on both ZETADYN 3C and ZAdyn4C The connecting lead can be...

Page 13: ...ZAdyn4C 2 CAN interface X CAN CAN interface X CAN CH 4 CH 4 3 3 CL 2 CL 2 0VC 1 0VC 1 Connection terminal X CAN ZETADYN 3C Connection terminal X CAN ZAdyn4C Encoder simulation X ENCO ZETADYN 3C ZAdyn...

Page 14: ...C ZAdyn4C 2 Brake bleed monitor X BR Brake air monitor X MON 24V_B 6 24V_B 13 BR1 5 BR1 12 BR2 4 BR2 11 BR3 3 BR3 10 BR4 2 BR4 9 1 Connection terminal X BR ZETADYN 3C Connection terminal X MON ZAdyn4C...

Page 15: ...nputs control Wire designation of the pre assembled connecting lead L SL xx HX ZA4 STO 1 Information only not safety related Connect the digital output O51 O54 STO Info of the ZAdyn4C to the motor con...

Page 16: ...ding parameters onto the ZAdyn4C Insert the memory card in the X MMC card slot see gures Memory card in the X MMC card slot of ZAdyn4C 011 032 Memory card in card slot X MMC on ZAdyn4C 040 074 Statist...

Page 17: ...r Radio interference filter L1 N PE Asynchronmotor Asynchronous motor Bremsl ft berwachung Brake release monitoring Aufzugsteuerung Elevator controller F1 F3 F2 Inkrementalgeber Incremental encoder Br...

Page 18: ...us motor Bremsl ft berwachung Brake release monitoring Aufzugsteuerung Elevator controller F1 F3 F2 Bremswiderstand Brake resistor X PAD ZETAPAD X GND Y Y CH 0VC CL X CAN X AN DA DB 0VD X DCP X X X EN...

Page 19: ...Circuit suggestion for ZAdyn4C ZD4C01K2 Technische Information R TIA14_12 GB 1528 Part No 19 22...

Page 20: ...oder BC menu Monitoring menu ENC_TYP MOD_ST ENC_INC STO BC_TYP LOCKBR R_BR Ohm CO P_BR kW BR T_PFU s P1P2 R_P1P2 Installation menu T_ENC V m s T_SDLY MOD_n T_CO n rpm T_CDLY _D m T_BR _iS S_MB _i1 I_M...

Page 21: ...eter set 2 V_Z F_PAR2 V_4 U_ACCU V_5 P_UPS V_6 RS_UPS V_7 STOP Copy Deceleration menu A_NEG Menu encoder calibration for synchronous motors R_NEG1 ENC_OFF R_NEG2 S_DI3 Menu CAN for CAN control S_DI2 L...

Page 22: ...nges Customer Service phone 49 7940 16 308 fax 49 7940 16 249 drives service ziehl abegg com Headquarters ZIEHL ABEGG SE Heinz Ziehl Strasse 74653 K nzelsau Germany phone 49 7940 16 0 fax 49 7940 16 2...

Reviews: