Toshiba XXXXXXX(<SanSerif1>X/X)
– 5 –
Digital Inverter
Outdoor Unit Installation Manual
Required Tools/Equipment and Precautions for Use
Prepare the tools and equipment listed in the following table before starting installation work.
Newly prepared tools and equipment must be used exclusively.
Legend
: Prepared newly (Use for R410A only. Do not use for refrigerant R22 or R407C etc..)
: Conventional tools/equipment are available
Refrigerant Piping
New refrigerant (R410A)
When using the conventional piping kit
• When using the conventional piping kit that has no indication of applicable refrigerant types, be sure to
use it with a wall thickness of 0.8 mm for Ø6.4 mm, Ø9.5 mm, and Ø12.7 mm, and with a wall thickness
of 1.0 mm for Ø15.9 mm. Never use the conventional piping kit with a wall thickness less than these
thicknesses due to insufficient pressure capacity.
When using general copper pipes
• Use general copper pipes with a wall thickness of 0.8 mm for Ø6.4 mm, Ø9.5 mm, and Ø12.7 mm, and
with a wall thickness of 1.0 mm for Ø15.9 mm.
Never use any copper pipes with a wall thickness less than these thicknesses.
Flare nuts and flare machining
• The flare nuts and flare machining are different from those for the conventional refrigerant.
Use the flare nuts supplied with the air conditioner or those for R410A.
• Before performing flare machining, carefully read “REFRIGERANT PIPING”
Tools/equipment
Use
How to use tools/equipment
Gauge manifold
Vacuuming/charging
refrigerant and operation
check
Prepared newly for R410A only
Charging hose
Prepared newly for R410A only
Charging cylinder
Can not be used
Unusable (Use the refrigerant charging measure
instead.)
Gas leak detector
Gas leak check
Prepared newly
Vacuum pump with backflow
prevention function
Vacuum drying
Unusable
Vacuum pump with backflow
prevention function
Vacuum drying
R22 (Conventional tools)
Flare tool
Flare machining of pipes
Usable if dimensions are adjusted.
Bender
Bending pipes
R22 (Conventional tools)
Refrigerant recovery equipment
Refrigerant recovery
For R410A only
Torque wrench
Tightening flare nuts
Exclusive for Ø12.7 mm and Ø15.9 mm
Pipe cutter
Cutting pipes
R22 (Conventional tools)
Refrigerant cylinder
Charging refrigerant
For R410A only
Discriminated by the refrigerant name on the
cylinder.
Welding machine and nitrogen
cylinder
Welding pipes
R22 (Conventional tools)
Refrigerant charging measure
Charging refrigerant
R22 (Conventional tools)
5-EN