– 25 –
4. Outdoor fan control
Allocations of fan tap revolutions [rpm]
SM561
SM801
SM1101
SM1401
W1
W2
W3
W4
W5
W6
W7
W8
W9
WA
WB
WC
WD
WE
WF
200
300
350
410
480
500
530
560
640
670
700
750
800
840
840
200
300
350
410
480
500
530
560
640
670
700
750
840
940
980
250
280
320
360
410
460
520
580
640
700
760
860
860
900
930
250
280
320
360
410
460
520
580
640
700
760
860
860
900
970
1) Cooling fan control
The outdoor fan is controlled by TE, TD, and TO sensors and also revolution frequency of the opera-
tion. The outdoor is controlled by every 1 tap of DC fan control (15 taps).
Only during 60 seconds after the operation has started, the fan is fixed with the maximum fan tap
which corresponds to the zone in the following table.
After then the fan is controlled by TE sensor temperature.
Considering a case that TE sensor has come out of the holder, the fan is controlled so that revolution
frequency of the fan increases regardless of TE if temperature of TD sensor has risen.
+1 tap/20 seconds
rpm hold
–1 tap/20 seconds
Operation with
maximum tap in
each zone
Usual fan control
a
b
TE [˚C]
TD [˚C]
85
80
75
65
Operation with WE
(The operation frequency differs according to the model type.)
SM561, SM801
SM1101, SM1101
a
b
36
32
29
26
Temp. range
29°C < TO
15 < TO < 29°C
5 < TO < 15°C
0 < TO < 5°C
TO < 0°C
TO error
Below 30Hz
Min
Max
W5
WA
W3
W7
W2
W5
W1
W3
W1
W2
W1
WF
Above 30 Hz below 45 Hz
Min
Max
W7
WC
W5
W9
W4
W7
W3
W5
W2
W4
W1
WF
Above 45 Hz
Min
Max
W9
WF
W7
WB
W6
W9
W4
W7
W3
W5
W1
WF