– 55 –
Operation of diagnostic function
Block
display
Check
code A
Check
code B
Cause of operation
Status of air
conditioner
Condition
Judgment and measures
Error in indoor fan system
Revolutions frequency
error of fan
All stop
Displayed when
error is detected
1. Check indoor fan motor connector
circuit (CN210).
2. Check indoor fan.
3. Check indoor P.C. board (Main P.C.
board).
Error in indoor unit or
other positions
1. EEPROM access error
Operation
continues
Displayed when
error is detected
1. Check indoor P.C. board
(EEPROM and peripheral circuits)
(Main P.C. board).
Outside error input
Detected by input voltage
level from outside devices
Operation
continues
Displayed when
error is detected
1. Check outside devices.
2. Check indoor P.C. board
(Main P.C. board).
[MODE] lamp
5Hz flash
Outside interlock input
Detected by input voltage
level from outside devices
All stop
Displayed when
error is detected
1. Check outside devices.
2. Check indoor P.C. board
(Main P.C. board).
Operation of diagnostic function
Check
code
Cause of operation
Status of air
conditioner
Condition
Judgment and measures
Serial return signal is not sent from
No. 1 indoor unit to remote controller.
• Miswiring of inter-unit wire between
remote controller and indoor unit
• Miss-setting of indoor unit No.
(Group address)
ON/OFF
Displayed when
error is detected
1. Indoor unit does not completely operate.
• Check inter-unit wire.
• Check indoor P.C. board. (Main/Sub P.C. boards)
• Check remote controller.
2. In normal operation
• Check setting of indoor unit No.
(SW01) (Sub P.C. board)
• Check remote controller.
Error mode detected by indoor unit (1)
Error mode detected by indoor unit (2)