– 40 –
Correct connection of connector.
Check drain pipe, etc.
Check and correct cabling/wiring.
Correct connection of connector.
Replace capacitor.
Replace fan motor
Replace TA sensor.
Check indoor P.C. board.
Defect
®
Replace
Check indoor P.C. board.
Defect
®
Replace
Check indoor P.C. board.
Defect
®
Replace
Check indoor P.C. board.
Defect
®
Replace
Correct connector
connection/wire circuit.
Replace drain pump.
Check cabling.
Is there no connection
error/disconnection
of CN076 connector?
* Refer to Characteristics-1.
NO
YES
NO
YES
NO
NO
NO
NO
YES
NO
YES
YES
YES
YES
YES
NO
Does float switch operate?
Is capacitor normal?
Does drain pump operate?
Is circuit cabling normal?
Is power of drain pump turned on?
Is connection of float switch connector
(Indoor control P.C. board CH34) normal?
Is there no mechanical lock
of fan motor?
NO
YES
Is connection of TA sensor connector
(indoor P.C. board CN104) normal?
NO
YES
Are characteristics of TA sensor
resistance value normal?
[P01 error]/[11 error]
[F10 error] [0C error]
[P10 error]/[Ob error]