– 12 –
5. SPECIFICATIONS OF ELECTRICAL PARTS
RAV-SM561AT-E, RAV-SM801AT-E
RAV-SM1101AT-E, RAV-SM1401AT-E
No.
1
2
3
4
5
6
7
8
9
10
11
Parts name
Fan motor
Compressor
Reactor
Outdoor temp. sensor (To-sensor)
Heat exchanger sensor (Te-sensor)
Suction temp. sensor (Ts-sensor)
Discharge temp. sensor (Td-sensor)
Fuse (Switching power (Protect))
Fuse (Inverter, input (Current protect)
4-way valve solenoid coil
Compressor thermo. (Protection)
Type
ICF-140-43-4
DA150A1F-20F
CH-57
—
—
—
—
VHV-01AJ503C1
US-622
Specifications
Output (Rated) 43 W
3 phase, 4P, 1100 W
10 mH, 16A
10 k
Ω
at 25°C
10 k
Ω
at 25°C
10 k
Ω
at 25°C
50 k
Ω
at 25°C
T3.15 A, AC 250 V
25 A, AC 250 V
ON : 90 ± 5°C, OFF : 125 ± 4°C
No.
1
2
3
4
5
6
7
8
9
10
11
Parts name
Fan motor
Compressor
Reactor
Outdoor temp. sensor (To-sensor)
Heat exchanger sensor (Te-sensor)
Suction temp. sensor (Ts-sensor)
Discharge temp. sensor (Td-sensor)
Fuse (Switching power (Protect))
Fuse (Inverter, input (Current protect))
4-way valve solenoid coil
Compressor thermo. (Protection)
Type
ICF-280-100-1
DA420A3F-21M
CH-56-2Z-T
—
—
—
—
VHV-01AJ503C1
US-622
Specifications
Output (Rated) 100 W
3 phase, 4P, 3750 W
6 mH, 18.5 A
10 k
Ω
at 25°C
10 k
Ω
at 25°C
10 k
Ω
at 25°C
50 k
Ω
at 25°C
T3.15 A, AC 250 V
25 A, AC 250 V
ON : 90 ± 5°C, OFF : 125 ± 4°C