Check
code
[F08]
[F12]
[F13]
[F15]
Outdoor
LED display
Check and troubleshooting
(Item without special mention Indicates part of outdoor unit.)
[Outside air temp. sensor (TO) error]
[Suction temp. sensor (TS) error]
[Heat sink temp. sensor (TH) error]
[Miss-mounting of outdoor temp. sensor (TE)
Correct connector.
Sensor error
→
Replace
Check outdoor P.C. board.
Defect
→
Replace
Is CN6
3
connection correct?
Is resistance value of TO sensor correct?
YES
NO
Correct connector.
Sensor error
→
Replace
Check outdoor P.C. board.
Defect
→
Replace
Is CN6
4
connection correct?
Is resistance value of TS sensor correct?
YES
NO
Check outdoor P.C. board.
Defect
→
Replace
Check outdoor P.C. board.
Defect
→
Replace
Correct connector.
Sensor error
→
Replace
Correct connector.
Sensor error
→
Replace
Correct sensor mounting.
Is mounting status of
TE and TS sensors correct?
Is CN6
4
connection correct?
Is resistance value of TS sensor correct?
Is CN6
1
connection correct?
Is resistance value of TE sensor correct?
YES
YES
YES
NO
NO
NO
–