8-2-4. Check Code List (Outdoor)
○
: ON,
◎
: Flash,
●
: OFF
ALT (Alternate): Alternate flashing when there are two flashing LED/SIM (Simultaneous): Simultaneous flashing when there are two fl
ashing LED
Central Control indication
Remote Controller indication
Sensor lamp part
Defected position
Detection
Explanation of error contents
Automatic
Reset
Operation continuation
Block indication
Operation Timer Ready
Flash
19
F04
◎
◎ ○
ALT
Outdoor unit Discharge temp. sensor (TD) error
Outdoor
Disconnection, short of discharge temp. sensor (TD) was detected
××
18
F06
◎
◎ ○
ALT
Outdoor unit heat exchanger temp. sensor (TE) error
Outdoor
Disconnection, short of outdoor unit heat exchanger temp. sensor (
TE) was detected.
××
1b
F08
◎
◎ ○
ALT
Outdoor unit Outside air temp. sensor (TO) error
Outdoor
Disconnection, short of outside air temp. Sensor (TO) was detected.
○○
A2
F12
◎
◎ ○
ALT
Outdoor unit Suction temp. sensor (TS) error
Outdoor
Disconnection, short of suction temp. Sensor (TS) was detected.
××
43
F13
◎
◎ ○
ALT
Outdoor unit Heat sink temp. sensor (TH) error
Outdoor
Disconnection, short of heat sink temp. Sensor (TH) (P.C. board install
ed) was detected.
××
18
F15
◎
◎ ○
ALT
Outdoor unit Miss-mounting of temp. sensor (TE, TS)
Outdoor
Miss-mounting of outdoor heat exchanger temp. sensor (TE) and suction temp. sensor(TS) was
detected.
××
1F
H01
●
◎ ●
Outdoor unit Compressor break down
Outdoor
Reached release point at min-Hz during compressor operating. Short-circuited current (Idc) was detected after DC excitation.
××
1d
H02
●
◎ ●
Outdoor unit Compressor lock
Outdoor
Compressor lock was detected.
××
17
H03
●
◎ ●
Outdoor unit Current detection circuit error
Outdoor
Current detection circuit error.
××
88
L10
◎
○ ◎
SIM
Outdoor unit Unset model type of service P.C. board
Outdoor
When outdoor service P.C .board was used, model type select jumper
setting was inappropriate.
××
1C
L29
◎
○ ◎
SIM
Outdoor unit error
Outdoor
1) Outdoor P.C. board part error was detected (EEPROM error, Heat sink temp. sensor (TH) error) 2) Outdoor unit Unset model type of service P.C. board. 3) Outdoor Heat sink overheat error, Gas leak detection, or 4-way valve system error.
××
1E
P03
◎
● ◎
ALT
Outdoor unit Discharge temp. error
Outdoor
Error was detected by discharge temp, release control.
××
21
P04
◎
● ◎
ALT
Outdoor unit High pressure SW system error
Outdoor
High pressure protection switch operated.
××
AF
P05
◎
● ◎
ALT
Power supply error
Outdoor
Power supply voltage error.
××
1C
P07
◎
● ◎
ALT
Outdoor unit Heat sink overheat error
Outdoor
Abnormal overheat was detected by outdoor heat sink temp. sensor (TH).
××
AE
P15
◎
● ◎
ALT
Gas leak detection
Outdoor
Abnormal overheat of discharge temp. sensor (TD) or suction temp. sensor (TS) was detected.
××
22
P20
◎
● ◎
ALT
Outdoor High pressure protective operation
Outdoor
Error was detected by high pressure release control from indoor / outdoor heat exchanger temp.
sensor.
××
1A
P22
◎
● ◎
ALT
Outdoor unit Outdoor fan system error
Outdoor
Error (Over-current, lock, etc.) was detected on outdoor fan drive circuit.
××
14
P26
◎
● ◎
ALT
Outdoor unit Short-circuit of compressor drive element
Outdoor
Short-circuited protective operation of compressor drive circui
t element (G-Tr / IGBT) operated.
××
16
P29
◎
● ◎
ALT
Outdoor unit Position detection circuit error
Outdoor
Position detection error of compressor motor was detected.
××
97
E01
◎
● ●
No remote controller master unit Remote controller communication error
Remote controller
Signal was not received from indoor unit. Main remote controller was not set. (including 2 remote controllers)
−−
−
E02
◎
● ●
Remote controller send error
Remote controller
Signal cannot be sent to indoor unit.
−−
97
E03
◎
● ●
Regular communication error between indoor and remote controller
Indoor
No communication from remote controller and network adapter
○×
04
E04
●
● ◎
Indoor/Outdoor serial error
Indoor
Serial communication error between indoor and outdoor
○×
96
E08
◎
● ●
Duplicated indoor addresses
Indoor
Same address as yours was detected.
○×
99
E09
◎
● ●
Duplicated main remote controllers
Remote controller
In 2-remote controller control, both were set as master. (Indoor master unit stops warning and follower unit continues operation.)
××
CF
E10
◎
● ●
Communication error between CPU
Indoor
MCU communication error between main motor and micro computer
○△
–
50
–
SVM-13072.indb 52
SVM-13072.indb 52
11/01/13 1:53 PM
11/01/13 1:53 PM
FILE NO. SVM-18042
-1