Item
12. Indoor fan
ON output
Operation flow and applicable data, etc.
ON signal is output when the indoor fan is operating.
1. Control items
• While the indoor fan is operating, DC12V is output between 1
and 6 of CN60.
2. Wiring
Description
A fan or etc can be used by
synchronized with the indoor unit.
3. Operation
• While the indoor fan operating, the output is ON.
• When thermo-off occurs during heating operation, the indoor
fan may perform ON/OFF operation. In this case, the output
keeps ON status.
• The lead wire, which connects the indoor P.C. board and the
relay, should be long within 2m. If using a longer wire or if not
using a relay, a malfunction may occur.
• The lead wire (length: 500mm) attached with connector, which
connects it to CN60 is prepared as article sold separately.
<Model: TCB-KBCN60OPE>
1
2
3
4
5
6
1
2
3
4
5
6
CN60
(6P)
Indoor
P.C. board
Relay
(Procured locally)
Within 2m
Red
Blue
Orange
Yellow
Brown
Black
1
2
3
4
5
6
500mm