Repair defective position.
Replace defective part.
Correct connector.
Sensor error
→
Replace.
Check outdoor P.C.B.
WP-041
and indoor C room P.C. board.
Defect
→
Replace.
Is PMV under correct conditions?
Check temp. sensor of C room indoor unit?
TA sensor, TC sensor
YES
NO
OK
Error
Repair defective position.
Replace defective part.
Correct connector.
Sensor error
→
Replace.
Check outdoor P.C.B.
WP-041
and indoor B room P.C. board.
Defect
→
Replace.
Is PMV under correct conditions?
Check temp. sensor of B room indoor unit?
TA sensor, TC sensor
YES
NO
OK
Error
Repair defective position.
Replace defective part.
Correct connector.
Sensor error
→
Replace.
Check outdoor P.C.B.
WP-041
and indoor A room P.C. board.
Defect
→
Replace.
Is PMV under correct conditions?
Check temp. sensor of A room indoor unit?
TA sensor, TC sensor
YES
NO
OK
Error
Check
code
Outdoor
LED display
Check and troubleshooting
(Item without special mention indicates part of outdoor unit.)
[20]
∗
There is a possibility that it is one of the following errors.
Confirm LED on
outdoor
P.C. board to judge which error it
is.
PMV error for A room, B room, C room
and D room.
[PMV error for A room]
[PMV error for B room]
[PMV error for C room]
{
:ON
(
{
*:3 sec ON / 0.5 sec OFF)
z
:OFF
{
*
*
*
z
z
{
*
*
z
{
*
*
*
[PMV error for D room]
Repair defective position.
Replace defective part.
Correct connector.
Sensor error
→
Replace.
Check outdoor P.C.B.
WP-041
and indoor D room P.C. board.
Defect
→
Replace.
Is PMV under correct conditions?
Check temp. sensor of D room indoor unit?
TA sensor, TC sensor
YES
NO
OK
Error
*
*
*
*
FILE NO. SVM-18052
- 87 -