–
40
–
FILE NO. SVM-09036
<
When the installation plate is directly
mounted on the wall
>
1. Securely fit the installation plate onto the wall by
screws with the upper and lower catches, that
hold the indoor unit, facing out.
2. To mount the installation plate on a concrete wall
use anchor bolts. Drill the anchor bolt holes as
illustrated in the above figure.
3. Install the installation plate horizontally and level.
CAUTION
Failure to securely install the unit may result in
personal injury and/or property damage if the
unit falls.
• In case of block, brick, concrete or similar type
walls, drill 5 mm dia. holes in the wall.
• Insert clip anchors for the
mounting screws.
NOTE :
• Install the installation plate using mounting screws
between 4 to 6, being sure to secure all four
corners.
Anchor bolt
Projection
15mm or less
5 mm dia. hole
Clip anchor
(local parts)
8
-
4
-3. Electrical Work
1. The supply voltage must be the same as the
rated voltage of the air conditioner.
2. Prepare a power source for the exclusive use of
the air conditioner.
NOTE :
• Wire type :
More than 1.5 mm
2
H07RN-F or 60245IEC66.
CAUTION
• This appliance can be connected to a main
circuit breaker in either of the following two
ways.
1. Connection to fixed wiring:
A switch or circuit breaker which discon-
nects all poles and has a contact separa-
tion of at least 3 mm must be incorporated
in the fixed wiring. An approved circuit
breaker or switch must be used.
2. Connection with power supply plug:
Attach power supply plug with power cord
and plug it into wall outlet. An approved
power supply cord and plug must be used.
NOTE :
• Perform wiring work being sure the wire length is
long enough.
8
-
4
-4. Wiring Connection
<
How to connect the connecting cable
>
Wiring the connecting cable can be carried
out without removing the front panel.
1. Remove the air inlet grille. Open the air inlet grille
upward and pull it toward you.
2. Remove the terminal cover and cord clamp.
3. Insert the connecting cable (or as according to
local regulations/codes) into the pipe hole on the
wall.
4. Pull the connecting cable through the cable slot
on the rear panel so that it protrudes about
15 cm out of the front.
5. Insert the connecting cable fully into the terminal
block and secure it tightly with screws.
6. Tightening torque: 1.2 N•m (0.12 kgf•m)
7. Secure the connecting cable with the cord clamp.
8. Attach the terminal cover, rear plate bushing and
air inlet grille on the indoor unit.
Installation plate
<Keep horizontal direction>
l
CAUTION
When installing the installation plate with mount-
ing screw, do not use the anchor bolt hole.
Otherwise the unit may fall down and result in
personal injury and property damage.
Fig.
8
-
4
-5
Fig.
8
-
4
-4
7 Mounting screw
Ø4 × 25