3
−
FILE NO. SVM-09036
1. SPECIFICATIONS
MODEL
RAS-18SKP-ES
RAS-24SKP-ES
RAS-18SA-ES
RAS-24SA-ES
ITEM
Cooling
Cooling
kW
Phase
V
Hz
Power consumption
W
Power factor
%
Running
A
Current
Indoor/Outdoor
Starting current
A
Moisture removal
lit/h
Noise
Indoor (H/M+/M/L+/L)
dB
Outdoor (220-240V)
dB
Refrigerant
Name of refrigerant
Rated amount
kg
Refrigerant control
Interconnection
Gas side size
mm
pipe
Connection type
Liquid side size
mm
Connection type
Maximum length
m
(One way)
Maximum height
m
difference
INDOOR UNIT
Dimensions
Height
mm
Width
mm
Depth
mm
Net weight
kg
Evaporator type
Indoor fan type
Airflow volume
High fan
m
3
/h
Medium fan
m
3
/h
Low fan
m
3
/h
Fan motor output
W
Air filter
OUTDOOR UNIT
Dimensions
Height
mm
Width
mm
Depth
mm
Net weight
kg
Condenser type
Outdoor fan type
Airflow volume
m
3
/h
Fan motor output
W
Compressor
Model
Output
W
Safety device
Louver type
Usable outdoor temperature range °C
2600
PA200X2CS-4KU1
1500
15 ~ 43
RAS-18SKP-ES
RAS-24SKP-ES
1000
880
20*
2
25*
2
8
10
56
57
1.65
15*
1
98
2450
93
0.3/7.30 0.3/
6.90 0.50/14.70 0.50/12.90
240V
220V
5.35
6.80
1
∅
220 - 240
50
1680
2410
Capacity
Power source
220V
5.30
240V
6.85
1640
98
97
44
2.7
31
2.0
44/42/39/37/35
45/43/41/39/37
56
57
R410A
1.70
Capillary tube
∅
12.7
Flare connection
∅
6.35
Flare connection
Fuse , IOL
320
1050
228
13
Finned tube
Cross flow fan
1100
950
850
750
30
Honeycomb woven filter with PP frame
RAS-18SA-ES
RAS-24SA-ES
Finned tube
715
780
290
50
45
Propeller fan
2400
2550
2450
Automatic louver
42
PA270X3CS-4MU2
2000
Note *1 Chargeless pipe
*2 Maximum pipe