– 22 –
Screw size and tightening torque
◆
Communication wire connection
Get the communication wire through the cutout on the side of the electrical control box and connect it to the communication wire
terminals, then fix it with the communication cable clamp.
Screw size and tightening torque
Screw size
Tightening torque
(N•m)
Power supply terminal
M6
2.3 to 2.7
Earth screw
M8
5.5 to 6.6
Screw size
Tightening torque
(N•m)
Communication wire terminal
M4
1.2 to 1.4
U1 U2 U3 U4 U5 U6
U
5
, U
6
: Communication wiring between outdoor units
U
3
, U
4
: Central control device
U
1
, U
2
: Communication wiring between Indoor / Outdoor unit
TO
INDOOR
UNIT
TO
CENTRAL
CONTROL
LER
TO
OUTDOOR
UNIT
Regulation of harmonic current
This equipment complies with IEC 61000-3-12 provided that the short-circuit power Ssc is greater than or equal to Ssc (*1)
at the interface point between the user’s supply and the public system. It is the responsibility of the installer or user of the
equipment to ensure, by consultation with the distribution network operator if necessary, that the equipment is connected
only to a supply with a short-circuit power Ssc greater than or equal to Ssc (*1)
Furthermore, when similar equipment or other equipment which may cause harmonic current emissions are to be
connected to the same interface point with this equipment, to reduce the risk of possible problems which may be caused
from addition of those harmonic current emissions, it is recommended to make sure that the short-circuit power Ssc at the
interface point is greater than the sum of the minimum Ssc required by all the equipment which will be connected to the
interface point.
Ssc (*1)
Model
Ssc (kVA)
MMY-MAP0804FT8(Z)(ZG)-E
1290
MMY-MAP1004FT8(Z)(ZG)-E
1560
MMY-MAP1204FT8(Z)(ZG)-E
1692
MMY-MAP1404FT8(Z)(ZG)-E
1942
43-EN
44-EN