Refrigerant piping
WARNING
•
If the refrigerant gas leaks during installation, ventilate the room.
If the leaked refrigerant gas comes into contact with fire, noxious gas may be generated.
•
After installation, check that the refrigerant gas does not leak.
If the refrigerant gas leaks into the room and comes into contact with fire such as a fan heater, stove, or kitchen range,
noxious gas may be generated.
Connection of refrigerant pipe
1. The refrigerant pipe connecting section is set in the
outdoor unit. Remove the front panel and the piping /
wiring panel. (M5: 9 pcs.)
• As shown in the illustration on the right, the hooks
are at the right and left sides of the front panel. Lift
up and remove the front panel.
2. Pipes can be drawn out forward or downward from the
outdoor unit.
3. When drawing out the pipe forward, draw it out to the
outside via the piping / wiring panel, and leave a space
of 500 mm or more from the main pipe connecting the
outdoor unit with the indoor unit, considering service
work or other work on the unit. (For replacing the
compressor, 500 mm or more space is required.)
4. When drawing out the pipe downward, remove the
knockouts on the base plate of the outdoor unit, draw
the pipes out of the outdoor unit, and perform piping on
the right / left or rear side. Downward length of the
balance pipe should be 5 m or less.
5. Wrap a wet cloth around the valve of the pipe
connector valve to keep it cool during brazing.
(If it is not cooled enough, the heat may affect the
packing in the valve and cause gas leaks)
(MAP080
✽
, MAP100
✽
)
(MAP120
✽
, MAP140
✽
)
Front panel
Piping / wiring panel
(Rear piping)
Drawing out downward
(Left piping)
(Right piping)
Drawing out forward
50
0
m
m
or
m
or
e
Hook
(Left
piping)
(Right
piping)
Wet cloth
Packed valve of
liquid side
Ball valve of suction
gas side
Packed valve of
balance pipe
Ball valve of
discharge gas side
Packed valve of
liquid side
Ball valve of suction
gas side
Packed valve of
balance pipe
Ball valve of
discharge gas side
REQUIREMENT
• For a brazing work of the refrigerant pipes, be sure to use nitrogen gas in order to prevent oxidation of the inside
of the pipes; otherwise clogging of the refrigerating cycle due to oxidized scale may occur.
• Use clean and new pipes for the refrigerant pipes and perform piping work so that water or dust does not
contaminate the refrigerant.
* Remove all flux after brazing.
• Be sure to use a double spanner to loosen or tighten the flare nut. If a single spanner is used, the required level
of tightening cannot be obtained. Tighten the flare nut with the specified torque. (If it is hard to loosen or tighten
the flare nut of the balance pipe or packed valve of the liquid side with a double spanner, loosen or tighten the
flare nut while holding the valve mounting plate with a spanner.)
Pipe connection method of valve at the gas side (Example)
MMY-
Draw-out forward
Draw-out downward
MAP080
✽
MAP100
✽
Suction-side
gas pipe
Cut the L-shaped pipe, then braze the
supplied attachment pipe and socket
procured locally.
Suction-side
gas pipe
Cut the L-shaped pipe, then braze the
supplied attachment pipe and socket
procured locally.
Discharge-
side gas pipe
Braze the supplied attachment pipe
and elbow procured locally.
Discharge-
side gas pipe
Braze the supplied attachment pipe
and socket procured locally.
Liquid pipe
Braze the supplied attachment pipe
and socket procured locally.
Liquid pipe
Braze the supplied attachment pipe
and socket procured locally.
Outer dia. of
copper pipe
Tightening torque (N•m)
9.5 mm
34 to 42
12.7 mm
49 to 61
15.9 mm
63 to 77
19.1 mm
100 to 120
Ball valve of discharge
gas side
Do not clamp the
service port with a
double spanner, doing
so may damage the
service port.
Do not apply refrigerating oil to the
surface of the flare.
Discharge-
side gas pipe
Liquid pipe
L-shaped
pipe
Balance
pipe
Suction-side
gas pipe
Section
to be
cut
Attachment
pipe
Pipe
Socket
Pipe
Pipe
Pipe
Attachment
pipe
Attachment
pipe
Socket
Elbow
Suction-side
gas pipe
Discharge-
side gas pipe
Liquid pipe
L-shaped
pipe
Suction-side
gas pipe
Suction-side
gas pipe
Section
to be
cut
Pipe
Socket
Pipe
Pipe
Attachment
pipe
Attachment
pipe
Socket
Pipe
Attachment
pipe
Socket
Balance
pipe
19-EN
20-EN