– 30 –
10
How to set up the cooling only indoor unit
When setting the specific indoor unit to Cooling Only
unit without connecting to the flow selector unit, setup
to the indoor unit to become the Cooling Only unit is
necessary. Perform setup in the following procedure.
Setup to the indoor unit is performed by handling the
wired remote controller.
Even if a wired remote controller is not used, attach a
wired remote controller for setup.
Change the setup with the wired remote controller
before using the air conditioner with a wireless remote
controller.
Change the setup during stop of the operation.
(Be sure to stop operation of the air conditioner.)
1
When pushing
+
+
buttons
simultaneously for 4 seconds or more, after
a while, the display part flashes as shown in
the figure.
Check that the displayed CODE No. is [10].
• If the CODE No. indicates one other than [10],
push
button to erase the display, and then
retry the operation from the first step.
(After pushing
button, the operation of
remote controller cannot be accepted after a
while.)
(* The display changes according to the indoor unit
model.)
2
In a group control, the firstly displayed
indoor unit No. becomes the header unit.
Every pushing
button (left side of the
button), the indoor unit No. in the group control is
displayed successively.
In this time, the position of the indoor unit of which
setup is to be changed can be confirmed because
the fan and louver of the selected indoor unit work.
3
Use
and
buttons of the set
temperature to specify the CODE No. [0F].
4
Use
and
buttons of the timer time to
select the setup data [0001].
5
Push
button. In this time, if the display
changes from flashing to lighting, the setup
completes.
• To change the setup of an indoor unit other than
the selected one, start operation from
Procedure
2
.
• In a group control, setup change of all the indoor
units in a group is necessary.
To change the setup of the set other than the
selected one, start again operation from
Procedure
2
.
CAUTION
Cooling Only and Heat pump cannot exist in the
same group.
• Pushing
button clears the set up contents
which have been already set.
In this case, retry from Procedure
2
.
No.
1
3
5 2
4
6
SETTING
DATA
SET
SET
CL
TEST
TEST
TEST
CODE No.
UNIT No.
SETTING
R.C.
No.
SETTING
DATA
SET
SET DATA
0000
0001
Cooling Only
setup
Heat pump
Cooling Only
CODE No.
UNIT No.
R.C.
No.
SETTING
SETTING
DATA
SET
Select an indoor unit of which setting is to be
changed.
SET
CL
6
When the setup finished, push
button.
(The setup is determined.)
Pushing
button deletes the display and returns
to normal stop status.
(For some time after
button has been pushed,
the operation of the remote controller cannot be
accepted.)
TEST
TEST
TEST
59-EN
60-EN
Summary of Contents for MMY-MAP0804FT8-E
Page 37: ...EH99889397 ...