– 26 –
CAUTION
Relay connector connection
Never connect relay connectors between the [U1, U2] and [U3, U4] terminals before completing address setting of all
the refrigerant lines. Otherwise, the addresses cannot be set correctly.
Manual address setting using the remote controller
Procedure when setting indoor units’ addresses first under the condition that indoor wiring has been completed and
outdoor wiring has not been started (manual setting using the remote controller)
▼
Wiring example of 2 refrigerant lines
In the example above, disconnect the remote controller connections between the indoor units and connect
a wired remote controller to the target unit directly before address setting.
Pair the indoor unit to set and the remote controller one-to-one.
Turn on the power.
1
Push and hold the
,
, and
buttons at the same time for more than 4 seconds.
LCD starts flashing.
Line (system) address
1
1
1
2
2
Indoor unit address
1
2
3
1
2
Group address
1
Header unit
2
Follower unit
2
Follower unit
2
Follower unit
2
Follower unit
Outdoor
unit
Outdoor
unit
Remote
controller
Indoor unit 1
Indoor unit 2
Indoor unit 3
Indoor unit 1
Indoor unit 2
Refrigerant line 1
Refrigerant line 2
ON / OFF
TEMP.
TIME
SET CL
FILTER
RESET TEST
TIMER SET
CODE No.
UNIT No.
SETTING
DATA
SET
R.C.
No.
11
4, 7, 10
2, 5, 8
3, 6, 9
1
SET DATA
CODE No.
SET
CL
TEST
<Line (system) address>
2
Push the TEMP.
/
buttons
repeatedly to set the CODE No. to
.
3
Push the TIME
/
buttons repeatedly to
set a system address.
(Match the address with the address on the
interface P.C. board of the header outdoor unit in
the same refrigerant line.)
4
Push
button.
(It is OK if the display turns on.)
<Indoor unit address>
5
Push the TEMP.
/
buttons
repeatedly to set the CODE No. to
.
6
Push the TIME
/
buttons repeatedly to
set an indoor unit address.
7
Push the
button.
(It is OK if the display turns on.)
<Group address>
8
Push the TEMP.
/
buttons
repeatedly to set the CODE No. to
.
9
Push the TIME
/
buttons repeatedly to
set a group address. If the indoor unit is
individual, set the address to
; header
unit, ;
follower
unit, .
10
Push the
button.
(It is OK if the display turns on.)
11
Push the
button.
The address setting is complete.
(
flashes. You can control the unit after
has disappeared.)
NOTE
1. Do not use address numbers
29
or
30
when setting
system addresses using the remote controller.
These 2 address numbers cannot be used on
outdoor units and the CODE No. [
E04
] (Indoor /
outdoor communication error) will appear if they are
mistakenly used.
2. If you set addresses to indoor units in 2 or more
refrigerate lines manually using the remote
controller and will control them centrally, set the
header outdoor unit of each line as below.
• Set a system address for the header outdoor unit
of each line with SW13 and 14 of their interface
P.C. boards.
• Turn off dip switch 2 of SW30 on the interface P.C.
boards of all the header outdoor units connected
to the same central control, except the unit that
has the lowest address. (For unifying the
termination of the wiring for the central control of
indoor and outdoor units)
• Connect the relay connectors between the [U1,
U2] and [U3, U4] terminals on the header outdoor
unit of each refrigerate line.
• After finishing all the settings above, set the
address of the central control devices. (For the
setting of the central control address, refer to the
installation manuals of the central control
devices.)
Individual
: 0000
Header unit
: 0001
In case of group
control
Follower unit
: 0002
SET
SET
}}
SET
TEST
SETTING
SETTING
51-EN
52-EN