101
8-7-8. Fan operation check in outdoor unit
This function is provided to check the fan operation of the outdoor unit by using switches on the interface P.C. board
in the outdoor unit. The frequency of the fan speed can be controlled by setting of the switches. Use this function
to check the operation or abnormal sound in the fan system. And, use this function while the system is stopped.
NOTE)
Do not use this function during operation of the compressor. It may damage the compressor.
[Operation]
(1) Set the switches SW01/SW02/SW03 on the interface P.C. board of the outdoor unit to [2/1/4].
(2) When [F. d] is displayed in 7-segment display [A], keep pressing the switch SW04 for 2 seconds or more.
(3) When [ 63 ] is displayed in 7-segment display [B], the fan starts operation. (Max. mode operation)
(4) After that, by changing the setup number of the switches SW02 and SW03, 7-segment display [B] and the fan
mode are changed.
(Mode output pattern of the fan is as follows.)
[Clear]
This function is cleared by one of the following operations.
(1) When SW01 setting number was changed to other number.
(2) Press-switch SW05 was pressed for 2 seconds or more.
SW02 SW03
7-segment display [B]
Fan mode
1
4
[ 63 ]
63
2
[ 62 ]
62
3
[ 61 ]
61
4
[ 60 ]
60
5
[ 59 ]
59
6
[ 58 ]
58
7
[ 57 ]
57
8
[ 56 ]
56
9
[ 55 ]
55
10
[ 54 ]
54
11
[ 53 ]
53
12
[ 52 ]
52
13
[ 51 ]
51
14
[ 50 ]
50
15
[ 49 ]
49
16
[ 48 ]
48
1
5
[ 47 ]
47
2
[ 46 ]
46
3
[ 45 ]
45
4
[ 44 ]
44
5
[ 43 ]
43
6
[ 42 ]
42
7
[ 41 ]
41
8
[ 40 ]
40
9
[ 39 ]
39
10
[ 38 ]
38
11
[ 37 ]
37
12
[ 36 ]
36
13
[ 35 ]
35
14
[ 34 ]
34
15
[ 33 ]
33
16
[ 32 ]
32
SW02 SW03
7-segment display [B]
Fan mode
1
6
[ 31 ]
31
2
[ 30 ]
30
3
[ 29 ]
29
4
[ 28 ]
28
5
[ 27 ]
27
6
[ 26 ]
26
7
[ 25 ]
25
8
[ 24 ]
24
9
[ 23 ]
23
10
[ 22 ]
22
11
[ 21 ]
21
12
[ 20 ]
20
13
[ 19 ]
19
14
[ 18 ]
18
15
[ 17 ]
17
16
[ 16 ]
16
1
7
[ 15 ]
15
2
[ 14 ]
14
3
[ 13 ]
13
4
[ 12 ]
12
5
[ 11 ]
11
6
[ 10 ]
10
7
[ 9 ]
9
8
[ 8 ]
8
9
[ 7 ]
7
10
[ 6 ]
6
11
[ 5 ]
5
12
[ 4 ]
4
13
[ 3 ]
3
14
[ 2 ]
2
15
[ 1 ]
1
16
[ 0 ]
0
Summary of Contents for MMY-MAP0724HT6UL
Page 229: ...228 15Exploded Diagram Parts Price List SMMS i OUTDOOR UNIT MMY MAP0724HT6UL ...
Page 230: ...229 MMY MAP0724HT6UL ...
Page 232: ...231 SMMS i OUTDOOR UNIT MMY MAP0964HT6UL MMY MAP1144HT6UL ...
Page 233: ...232 MMY MAP0964HT6UL MMY MAP1144HT6UL ...
Page 237: ...236 SMMS i INV SERVICE PARTS LIST MMY MAP0724HT6UL 4 pieces PC board ...
Page 238: ...237 SMMS i INV SERVICE PARTS LIST MMY MAP0964HT6UL MMY MAP1144HT6UL 4 pieces PC board ...
Page 241: ...Copyright 2011 TOSHIBA CARRIER CORPORATION ALL Rights Reserved ...