218
11 Transformer
WARNING
• Wear gloves.
Failure to wear gloves creates the risk of
personal injury by part replacement and
other objects.
• Do not attempt to modify the transformer.
1. Disassembly procedure
1) Stop operation of the outdoor unit and turn
off the breaker.
2) Remove the anchor plate screws.
(M5 x 0.4' (10mm), 4pcs)
3) Remove the screws that secure the base
assembly and transformer housing.
(M4 x 0.3' (8mm), 2pcs)
4) Shift the transformer housing slightly and
then remove the lead bundle band.
5) Lift up the transformer housing and move it
to a flat surface.
6) Remove the housing front cover screws.
(M4 x 0.2' (6mm), 6pcs)
7) Detach both the Faston terminals and
round terminals.
(Caution: When unplugging a Faston
terminal, grasp the wire at the base of the
terminal.)
8) Remove the leads from the holder.
9) Remove the shield screws and then
remove the shield.
(M4 x 0.3' (8mm), 3pcs)
No. Part to be replaced
Work procedure
Remarks
Screw tightening locations
for housing
2) M5 screws
Anchor plate
SMMS-i back
Enlarged view
3) M4 screws
4) Screw tightening locations for
front cover
Screw tightening locations for
front cover
6) M4 screws
6) M4 screws
Front cover
9) M4 screws
Left side
Shield
8) Holder
9) M4 screw
Right side
7) Faston
terminal
7) Round terminal
Summary of Contents for MMY-MAP0724HT6UL
Page 229: ...228 15Exploded Diagram Parts Price List SMMS i OUTDOOR UNIT MMY MAP0724HT6UL ...
Page 230: ...229 MMY MAP0724HT6UL ...
Page 232: ...231 SMMS i OUTDOOR UNIT MMY MAP0964HT6UL MMY MAP1144HT6UL ...
Page 233: ...232 MMY MAP0964HT6UL MMY MAP1144HT6UL ...
Page 237: ...236 SMMS i INV SERVICE PARTS LIST MMY MAP0724HT6UL 4 pieces PC board ...
Page 238: ...237 SMMS i INV SERVICE PARTS LIST MMY MAP0964HT6UL MMY MAP1144HT6UL 4 pieces PC board ...
Page 241: ...Copyright 2011 TOSHIBA CARRIER CORPORATION ALL Rights Reserved ...