164
(1)Display of System Information (Displayed on Header Outdoor Unit Only)
SW01 SW02 SW03
Display detail
1
1
3
Unused
A
B
2
System capacity
A […6]~[10]:6 to 20 ton
B [ton]
3
No. of outdoor units
A […1]~[…2]:1 to 2
B […P]
4
No. of indoor units connected /
No. of units with cooling thermo ON
A […0.]~[48.]:0 to 48 (No. of units connected)
B [C…0]~[C48]:0 to 48 (No. of units with cooling thermo ON)
5
No. of indoor units connected /
No. of units with heating thermo ON
A […0.]~[48.]:0 to 48 (No. of units connected)
B [H…0]~[H48]:0 to 48 (No. of units with heating thermo ON)
6
Amount of compressor command
correction
A Value displayed in hexadecimal format
B
7
Release control
A Normal: [r. …], During release control: [r.1]
B –
8
Oil equalization control
Normal: [oiL-0]
During oil equalization control: [oiL-1]
9
Oil equalization request
A Displayed through LED segment lighting pattern
B
10
Refrigerant/oil recovery operation
A Oil recovery in cooling: [C1], Normal: [C …]
B Refrigerant recovery in heating: [H1], Normal: [H …]
11
Automatic addressing
A [Ad]
B During automatic addressing: [… FF], Normal: [… … …]
12
Power pick-cut
A [dU]
B Normal: [… … …], During 50-90% capacity operation: [_50-_90]
While control is based on BUS line input: [E50-E90]
13
Optional control (P.C. board input)
Displays optional control status
A
B
Operation mode selection: During priority heating (normal)
h.
∗
.
∗
.
∗
.
∗
.
Priority cooling
c.
∗
.
∗
.
∗
.
∗
.
Heating only
H.
∗
.
∗
.
∗
.
∗
.
Cooling only
C.
∗
.
∗
.
∗
.
∗
.
Priority given to No. of indoor units in operation
n.
∗
.
∗
.
∗
.
∗
.
Priority given to specific indoor unit
U.
∗
.
∗
.
∗
.
∗
.
External master ON/OFF: Normal
∗
.….
∗
.
∗
.
∗
.
Start input
∗
.1.
∗
.
∗
.
∗
.
Stop input
∗
.0.
∗
.
∗
.
∗
.
Night operation: Normal
∗
.
∗
.
….
∗
.
∗
.
Start input
∗
.
∗
.
1.
∗
.
∗
.
Snowfall operation: Normal
∗
.
∗
.
∗
.….
∗
.
Start input
∗
.
∗
.
∗
.1.
∗
.
14
Optional control
(BUS line input)
Same as above
15
Unused
16
–
A –
B –
Display section A Display section B
Outdoor unit No.
If element F shown on sketch at right turned on:
Header unit oil equalization request
If element C shown on sketch at right turned on:
Follower unit oil equalization request
Summary of Contents for MMY-MAP0724HT6UL
Page 229: ...228 15Exploded Diagram Parts Price List SMMS i OUTDOOR UNIT MMY MAP0724HT6UL ...
Page 230: ...229 MMY MAP0724HT6UL ...
Page 232: ...231 SMMS i OUTDOOR UNIT MMY MAP0964HT6UL MMY MAP1144HT6UL ...
Page 233: ...232 MMY MAP0964HT6UL MMY MAP1144HT6UL ...
Page 237: ...236 SMMS i INV SERVICE PARTS LIST MMY MAP0724HT6UL 4 pieces PC board ...
Page 238: ...237 SMMS i INV SERVICE PARTS LIST MMY MAP0964HT6UL MMY MAP1144HT6UL 4 pieces PC board ...
Page 241: ...Copyright 2011 TOSHIBA CARRIER CORPORATION ALL Rights Reserved ...