(8) Set Bits 1 and 2 of SW30 on the interface P.C. board same as that of the failed header unit (terminator
resistance setting).
[Wiring changes to communication line]
(9) Redirect the indoor-outdoor communication line connected to the failed header unit [U1/U2] to the unit selected
as the header unit [U1/U2].
(10)If a central control device is connected, connect the central control communication line [U3/U4] to the
communication line terminal of the unit selected as the new header unit [U3/U4], and connect up the tie
connector between the [U1/U2] and [U3/U4] terminals.
(11)Turn on the power supply to all the units connected to the system other than the failed unit.
Determine what to do with the power supply to the failed unit in the following manner.
<In case of fault in compressor, electrical part, I/F P.C. board, or IPDU P.C. board>
Leave the power supply off.
<In case of fault in refrigerating circuit or related part (pressure sensor, temperature sensor, refrigerating cycle
part, or fan system part)>
Turn on the power supply to protect the compressor (by turning on the case heater).
(When the power supply to the unit is turned on, [E19] (error in the number of outdoor header units) will be
displayed on the 7-segment display. However, this will not cause any problems.)
This is the end of header outdoor unit backup operation setting. Check the operation.
Set Bits 1 and 2 of SW30
identically to failed header unit.
Turn on Bit 2 of SW09.
Outdoor interface P.C. board of unit selected as new header unit
Set SW13 and SW14
identically to failed header unit.
Failed header unit
Unit selected as new header unit
(previously follower unit No. 1)
Central control communication line
(U3/U4 terminal)
Outdoor-outdoor communication line
(U1/U2 terminal)
Redirect the indoor-outdoor communication
line from failed header unit to unit selected
as header unit [U1/U2].
If central control device is connected, redirect central
control communication line from failed header unit to
unit selected as new header unit [U3/U4].
Outdoor-outdoor communication line (U5/U6)
Summary of Contents for MMY-MAP0724HT6UL
Page 229: ...228 15Exploded Diagram Parts Price List SMMS i OUTDOOR UNIT MMY MAP0724HT6UL ...
Page 230: ...229 MMY MAP0724HT6UL ...
Page 232: ...231 SMMS i OUTDOOR UNIT MMY MAP0964HT6UL MMY MAP1144HT6UL ...
Page 233: ...232 MMY MAP0964HT6UL MMY MAP1144HT6UL ...
Page 237: ...236 SMMS i INV SERVICE PARTS LIST MMY MAP0724HT6UL 4 pieces PC board ...
Page 238: ...237 SMMS i INV SERVICE PARTS LIST MMY MAP0964HT6UL MMY MAP1144HT6UL 4 pieces PC board ...
Page 241: ...Copyright 2011 TOSHIBA CARRIER CORPORATION ALL Rights Reserved ...