8-4-4. Check after address setup when central control system is
connected
When the central control system is connected, check that the following setup has finished after address setup.
NOTE
The figure above does not show all the electric wires.
For details, refer to the installation manuals for the outdoor unit, indoor unit, remote control, or optional devices.
Main check items
Check
Relay
connector
(1) Is the relay connector of the header unit connected after address setup?
(2) Is the relay connector of the follower unit removed?
Terminal
resistance
(3) Is the end resistance (SW30-bit 2) of the header unit with the smallest line address number
in the central control turned on? (Setup is unnecessary for follower units.)
(4) Is the terminal resistance (SW30-bit 2) of the header units, except for the line with the
smallest central control line address, turned off? (Setup is unnecessary for follower units.)
Line address (5) Are addresses in the line address (SW13, SW14) not duplicated in each refrigerant line?
Central remote
control
Other refrigerant line
Header unit (A)
Outdoor unit
Indoor unit
Header unit (A)
Follower unit (B)
Follower unit (C)
Remote
control
Remote
control
Remote
control
Line address = 2
Line address = 1
To other refrigerant line
Summary of Contents for MMY-MAP0724HT6UL
Page 229: ...228 15Exploded Diagram Parts Price List SMMS i OUTDOOR UNIT MMY MAP0724HT6UL ...
Page 230: ...229 MMY MAP0724HT6UL ...
Page 232: ...231 SMMS i OUTDOOR UNIT MMY MAP0964HT6UL MMY MAP1144HT6UL ...
Page 233: ...232 MMY MAP0964HT6UL MMY MAP1144HT6UL ...
Page 237: ...236 SMMS i INV SERVICE PARTS LIST MMY MAP0724HT6UL 4 pieces PC board ...
Page 238: ...237 SMMS i INV SERVICE PARTS LIST MMY MAP0964HT6UL MMY MAP1144HT6UL 4 pieces PC board ...
Page 241: ...Copyright 2011 TOSHIBA CARRIER CORPORATION ALL Rights Reserved ...