25
6-2. Outdoor unit
HWS-P805HR-E, P1105HR-E
6-3. Hot water cylinder unit
O ······· Applied
No.
Component name
Type name
Rating
1
Compressor
DA422A3F-26M
2
Outdoor fan motor (x2)
ICF-280-A100-1
Output 100 W
3
Reactor (x2)
CH-44
1.4 mH, 25 A
4
4-way valve coil
STF-H01AP1874A1
AC220 - 230 V full-wave rectifier input, alive time 10 sec or less
5
Pulse motor valve (PMV) coil
UKV-A038
DC12 V
6
Compressor case thermostat
US-622KXTMQO-SS
OFF = 125 ± 4 °C, ON = 90 ± 5 °C
7
PC board
MCC-1571
Input 1Ø, AC220 - 230 V ± 10%, 50/60 Hz
8
High pressure sensor
NSK-BH042D-430
0 ~ 4.15 MPa
9
2-way valve coil
VPV-MOAJ510B0
AC220 - 240 V
10
High pressure switch
ACB-4UB154W
OFF = 4.15 + 0, -0.15 MPa
No.
Component name
Model name
Type name
Rating
1501
CSH
M3-E
(-UK)
2101
CSH
M3-E
(-UK)
3001
CSH
M3-E
(-UK)
1
Hot water cylinder heater
O
O
O
–
AC230 V 2.7 kW
2
Hot water cylinder temperature
sensor
(TTW sensor)
O
O
O
–
10 k
Ω
(25 °C)
3
Thermal cut-out
O
O
O
–
Operating temperature
Manual reset 82 °C (+3K/-2K)