24
HWS-P1105XWHM3-E, T6-E, T9-E
O ······· Applied
OP ····· Optional accessory
No.
Component name
Model name
Type name
Rating
M3-E T6-E T9-E
1
Circulation pump
O
O
O
UPM GEO 25-85 130 AC230 V 0.66 A (MAX)
2
Backup heater 3 kW
O
SA3-23652B
AC230 V 3 kW
3
Backup heater 6 kW
O
SA3-23652B
AC400 V (3N) 6 kW
4
Backup heater 9 kW
O
SA3-23652B
AC400 V (3N) 9 kW
5
Water heat exchange
temperature sensor
(TC sensor)
O
O
O
–
10 k
Ω
(25 °C)
6
Water inlet temperature sensor
(TWI sensor)
O
O
O
–
10 k
Ω
(25 °C)
7
Water outlet temperature sensor
(TWO sensor)
O
O
O
–
10 k
Ω
(25 °C)
8
Heater outlet water temperature
sensor
(THO sensor)
O
O
O
–
10 k
Ω
(25 °C)
9
Floor inlet temperature sensor
(TFI sensor)
O
O
O
–
10 k
Ω
(25 °C)
10
Low pressure sensor
O
O
O
–
Operating pressure 0.20 MPa
11
Thermal protector (auto)
O
O
O
–
Operating temperature 75±3 °C DC42 V / 0.2 A
12
Thermal protector (single
operation)
O
O
O
–
Operating temperature 95±5 °C AC250 V 16 A
13
Flow switch
O
O
O
–
Operating flowing quantity 18 L/min
14
Output board (OP)
OP
OP
OP
TCB-PCIN3E
AC230 V 0.5 A, DC24 V 1 A
15
Input board (OP)
OP
OP
OP
TCB-PCM03E
Contact input
16
Remote controller (Main)
O
O
O
HWS-AMS54E
17
Remote controller (Sub)
OP
OP
OP
HWS-AMS54E
18
Water 3-way valve terminal
O
O
O
–
AC230 V 0.1 A
2Wire, 3Wire SPST, SPDT type mountable
19
Water 2-way valve terminal
O
O
O
–
AC230 V 0.1 A 2Wire type mountable
20
Mixing valve terminal
O
O
O
–
AC230 V 0.1 A
3Wire SPST, SPDT type mountable
21
Circulation pump terminal
O
O
O
–
AC230 V 1.0 A
22
Booster heater terminal
O
O
O
–
AC230 V 1.0 A
23
Fuse
O
O
O
–
AC250 V 30 A
Summary of Contents for HWS-P1105HR-E
Page 183: ...182 ...