147
16-2. Outdoor unit settings (Existing piping, Power save, etc.)
The following settings are available with dip switch setting and jumper wire setting.
Function
Where to set
Control details
Existing piping
setting
When using a Ø19.1 pipe for the existing piping, set the switch to ON.
This case may decrease heating capacity depending on the outside air
temperature when heating or on a room temperature.
Power save setting
When using the power save function, set the switch to ON. This setting
controls the compressor frequency lowering (about 10%) according to the
heat exchange temperature of the hydro unit during a heating or hot water
supply operation.
Snow prevention
fan control
This control enables the function that prevents snow from entering the draft
air duct through the fan guard or a heat exchanger gap and causing motor
lock. If the outside air temperature is 0 °C below, this control operates the
outdoor fan in W5 even if the compressor is not in operation.
Defrosting time
change
J805, J806
If the defrosting interval is shorter than the standard, the jumper wire is cut.
For the control details or how to cut the jumper wire, see defrosting control.
Maximum
frequency change
J807
If the maximum value of compressor frequency need to be lowered, cut the
jumper wire shown on the left.
This control lowers the maximum frequency when hot water supply, heating,
or cooling is in operation.
In this case, the maximum capacity decreases.
Maximum frequency of compressor
1234
ON
SW802
--- OFF
--- Existing piping setting
--- Power save setting
--- Snow prevention fan control
* All OFF position at factory default
Model
P805HR-E
P1105HR-E
Cooling
Heating
Cooling
Heating
Standard
37.2 70.2 53.4
90.0
J807
cut
33.0 63.0 48.0 81.0