116
9-6-2. Outdoor unit
No.
Component name
Check procedure
1
Compressor
Type
DA422A3F-26M
Measure the resistance value of each winding with a tester.
2
Outdoor fan motor
Type
ICF-280-A100-1
Measure the resistance value of each winding with a tester.
3
4-way valve coil
Type
STF-H01AP1874A1
Measure the resistance value.
1617
Ω
± 113
Ω
4
2-way valve coil
Type
VPV-MOAJ510B0
Measure the resistance value.
1435
Ω
± 144
Ω
5
Pulse motor valve coil
Type
UKV-A038
6
Suction temperature (TS) sensor
Heat exchange temperature
(TE) sensor
Outdoor temperature (TO)
sensor
Remove the connector and measure the resistance value with a tester.
10-20 k
Ω
(Normal temperature)
7
Discharge temperature (TD)
sensor
Remove the connector and measure the resistance value with a tester.
Red
White
Black
Location
Resistance
value
Red
−
White
1.04-1.16
Ω
White
−
Black
1.04-1.16
Ω
Black
−
Red
1.04-1.16
Ω
At 20 °C
Red
White
Black
Location
Resistance value
Red
−
White
14.8 ± 1.5
Ω
White
−
Black
Black
−
Red
M
1 Black
6 Grey
3 Red
Yellow
2
Grey
6
Orange
4
Location
Resistance
value
Grey
−
Black, Red
43-49
Ω
Grey
−
Yellow, Orange
43-49
Ω
Condition 20 °C
Temperature
0 °C
10 °C
20 °C
30 °C
Sensor (k
Ω
)
Outdoor heat exchange temperature sensor (TE)
33.8
20.4
12.6
8.0
Suction temperature sensor (TS)
Temperature
0 °C
10 °C
20 °C
30 °C
Sensor (k
Ω
)
Discharge temperature sensor (TD)
161.3
99.0
62.4
40.2