150
13
Flow switch
1. How to remove
1) Perform the step 1-1 and step 5.
2) Remove the flow switch.
2. How to attach
1) Attach a new flow switch in the reverse order of the
removal.
NOTE
As shown on the right,
place a flow sensor parallel to the water heat exchanger
inlet pipe so that the wire is place on the right side from
the front view.
14
Manometer
1. How to remove
1) Perform the step 1-1 and step 5 and 6.
2) Remove the manometer.
No.
Exchange parts name
Work procedure
Remarks
To replace a water circuit part, first close the water
supply source valve and the valve of water pipe
connected to the hydro unit.
The flow switch connection uses an O ring for water
seal. Be careful not to scratch the O ring; otherwise,
water leakage may occur.
After the flow switch replacement repair, open the
water supply source valve and water piping valve to
pass water through the hydro unit, and check that
the flow switch connection has no water leakage.
Flow switch
Flow switch
Flow switch
Flow switch
Water heat inlet pipe
Water heat inlet pipe
Flow switch
Flow switch
Water heat inlet pipe
To replace a water circuit part, first close the water
supply source valve and the valve of water pipe
connected to the hydro unit.
After the manometer replacement repair, open the
water supply source valve and water piping valve to
pass water through the hydro unit, and check that
the manometer connection has no water leakage.
Manometer
Manometer
Manometer