3. Test run
<Procedure>
A test run is available with an actual operation in progress or stopped. A test run is available in any of the hot water
supply, heating, or cooling mode. The compressor starts according to the test run frequency. A test run
automatically stops after 30 minutes at the longest if not stopped with the remote controller.
1
Press the remote controller TEST
button for 4 seconds or
longer to display "TEST" on the LCD screen.
<For hot water supply test run>
2
Press the HOT WATER
button, and a hot water supply
operation starts after 3 minutes. (See display
)
(The pump immediately starts.)
3
Pressing the HOT WATER
button again stops the hot
water supply operation.
<For heating test run>
1
Press the ZONE1,2
button, and a heating operation
starts after 3 minutes. (See display
)
(The pump immediately starts.)
2
Pressing the ZONE1,2
button again stops the heating
operation.
<For cooling test run>
2
Press the ZONE1,2
button and then OPERATE MODE
, and a cooling operation starts after 3 minutes.
(The pump immediately starts.)
(See display
)
3
Pressing the ZONE1,2
button again stops the cooling
operation.
4
Press TEST
on the remote controller to exit the test run
mode.
1, 4
2, 3
1, 4 2, 3
1, 4 3
2