122
Remote controller function code table
A5
Set temperature E' with outside temperature of 20 °C
0020: 20 °C
-
0060: 60 °C
0020: 20 °C
B2
HP restart water temperature in A zone. (Valid only
room temp control using 2nd remote controller)
0020: 20 °C
0037: 37 °C
0025: 25 °C
B5
Initial water temperature setting method when
controlling heating by the room temperature remote
controller and room temperature thermostat
0000: The fixed temperature by FC9D
0001: The calculated temperature by Auto curve
0000: The fixed
B6
Changing the target of stopping / starting by external
signal (CN210 - terminal 2 and 3)
0000: none (Local hot water tank thermostat)
0001: Hot water supply control *4
0000: none
B8
Forcibly heater off at T0
≥
A °C
0000: no restriction, 0001: 20 °C
0002: 15 °C, ···, 0006: -5 °C
0000: no restriction
B9
Backup heater energization temperature during
defrosting.
Correction coefficient B
0000: 0K, ···, 0004: 40K
0000: 0K
BA
Intermittent operation at T0
≥
A °C
0000: continuous operation
0001: 20 °C, ···, 0006: -5 °C
0000: continuous
operation
BB
Intermittent operation at T0 < B °C
0000: continuous operation
0001: 35 °C, ···, 0003: 25 °C
0000: continuous
operation
BC
Pump off time during thermostat off operation
0000: 5 min, ···, 0005: 30 min
0000: 5 min
FC
Item
Details
Fist shipment
02
Temperature correction by the room temperature sensor
(heating)
-10K~+10K: By 1K steps
-1: -1K correction
03
Temperature correction by the room temperature sensor
(cooling)
-10K~+10K: By 1K steps
-1: -1K correction
05
24H/12H display switching
0: 24H display
1: 12H (AM/PM) display
0: 24H display
09
Night time low-noise mode
0: Invalid
1: Valid
0: Invalid
0A
Night time low-noise start time
0 - 23 (0:00 to 23:00)
22: 22:00
0B
Night time low-noise end time
0 - 23 (0:00 to 23:00)
06: 06:00
0C
Anti bacteria start time
0 - 23 (0:00 to 23:00)
22: 22:00
0D
Anti bacteria start cycle
1 - 10 (Every day to 10-day cycle)
07: 7-day cycle
0E
Starting time of Night set back
0 - 23 (0:00 to 23:00)
22: 22:00
0F
Ending time of Night set back
0 - 23 (0:00 to 23:00)
06: 06:00
11
Remote controller Alarm Tone.
0: Alarm Tone OFF
1: Alarm Tone ON
1: Alarm Tone ON
12
Frost running period (days)
(0 days – 20 days)
00: No setting
13
Frost running period (hours)
(0 hours – 23 hours)
00: No setting
FC
Item
Details
Factory default
*1 FC_01 is needed for PCB replacement or function code reset procedure has been completed.
*2 System restart with remote controller.
*3 Restart in the mode when stopping.
*4 In addition, it is enable only when switch 2-3 is set to “OFF” and FC61 is set to “3”.