113
9-4-3. Temperature sensor, temperature-resistance characteristic
table
TC, TWI, TWO, TFI, TTW, TE, TS, TO sensors
TD, TL sensors
Typical value
Typical value
Temperature
(°C)
Resistance value (k
Ω
)
Temperature
(°C)
Resistance value (k
Ω
)
(Minimum)
(Standard)
(Maximum)
(Minimum)
(Standard)
(Maximum)
-10
55.42
55.73
60.04
0
150.5
161.3
172.7
0
32.33
33.80
35.30
10
92.76
99.05
105.6
10
19.63
20.35
21.09
20
58.61
62.36
66.26
20
12.23
12.59
12.95
25
47.01
49.93
52.97
25
9.75
10.00
10.25
30
37.93
40.22
42.59
30
7.764
7.990
8.218
40
25.12
26.55
28.03
40
5.013
5.192
5.375
50
17.00
17.92
18.86
50
3.312
3.451
3.594
60
11.74
12.34
12.95
60
2.236
2.343
2.454
70
8.269
8.668
9.074
70
1.540
1.623
1.709
80
5.925
6.195
6.470
80
1.082
1.146
1.213
90
4.321
4.507
4.696
90
0.7740
0.8237
0.8761
100
3.205
3.336
3.468
100
0.5634
0.6023
0.6434
0
-10
0
10
20
30
40
50
60
10
20
30
40
50
60
70
80
90
100
0
0
0
5
10
15
20
50
100
150
200
10
20
30
40
50
60
70
80
90
100
Resistance (k
Temperature (°C)
TC, TWI, TWO, TFI, TTW, TE, TS, TO sensors
Resistance (k
) (50
°C
or lower)
Resistance (k
) (50
°C
or higher)
Temperature (°C)
TD, TL sensors
* Since the TH sensor (outdoor unit heat-sink temperature sensor) is built in the
outdoor control board, the resistance value cannot be measured.
AMP Air Conditioning
www.ampair.co.uk | [email protected]