A5.Operating Instructions for Specific Modules
Unified Controller nv series G3 I/O Adapter GA932 Module Instruction Manual
61
A.5 Operating Instructions for Specific Modules
1. TOSLINE-F10
TOSLINE-F10 module (MS311) does not support
for issuing commands for
communication stop/prohibit request using SW register.
For MS311 connected to
GA932 issues a command using the WRITE command. Also, check the status using
the READ command.
To issue a specific command, read Status 1 of MS311 using the READ command.
After that, take the logical OR of the read value and the command bit (8th bit for a
communication request, 9th bit for an output prohibition request). Issue a
command by writing the result of the logical OR to Status 1 of MS311 using the
WRITE command.
Figure A-1 Reading Status 1 by using the READ command for MS311
Figure A-2 Creating the logical OR of the value read from Status 1 and the
command request bit
F10 status read
Communication stop request data
generation
/* Communication stop request
:
8th bit = ON */
/* Output prohibition request
:
9th bit = ON */