A.2. Function Specifications
Unified Controller nv series G3 I/O Adapter GA932 Module Instruction Manual
55
each module. The recommended replacement cycle is 5 years. The base unit and the module except for
options which are applying aluminum electrolytic capacitor which is a lifetime part should be replaced for
each module. The recommended replacement cycle is 10 years.
A.2 Function Specifications
Table A-2 shows the function specifications.
Table A-2 GA932 function specifications
Classification
Item
Specification
Diagnostic
specification
RAS function
Power fail, I/O validity check, I/O installation check, I/O
bus check, Watchdog timer error, bus timeout error etc.
Module
specification
Redundancy
No redundancy
Online maintenance
Plug in or out at power ON
Dimensions
35 * 249 * 109mm
Weight
Approx.450g
Current consumption (Rated power
input)
1.5A or less
(
at 5.0Vdc
)
Connection
specification
Support controller
type1 light PUM12
Number of Nodes can be registered
1 Node/controller
Configurable Node No.
3
~
14 (03h
~
0Eh)
Number of occupied Nodes
1 Node
Installed base unit
T3/T3H Basic base unit (BU31A or BU315)
Number of maximum expansion units 6 units(3 units/2 lines per line)
Number of maximum I/O slots
76 slots
・
10 slots (basic unit)
・
11 slots(expansion unit) x6 units
Number of maximum I/O pts
4864 pts(64 pts when I/O used)
Applicable extended interface module
IF311
:
for basic unit
(
Standard: for 1 system
)
IF321
:
for basic unit
(
Standard: for 2 system
)
IF351
:
for expansion unit
(
Standard
)
IF312
:
for basic unit
(
Long distance type
)
IF352
:
for expansion unit
(
Long distance type: for
relay
)
IF353
:
for expansion unit
(
Long distance type: for
termination
)
Cable length between extended units
Standard: Maximum 2m
Long distance type: Maximum 40m
Total extension of extended cable
connection
Standard: Maximum 6m
Long distance type: Maximum 40m
Extended unit power supply
Standard: Yes
Long distance type: No (Power modules must be
installed on all expansion units.)
Performance
I/O input/output update time
10ms
or Approx. 2
+(
0.016
×
word
)
ms
(
*1
)
(
*1
)
See Figure 1-4 in 1.1.2 and the figure below. For the collective input/output performance of PUM12,
Refer to “Unified Controller nv series type 1 light Controller Unit User’s Manual -Functions-(6F8C1498)
Words
Applox.500 words
10ms
I/O update time
(Scan cycle)
Summary of Contents for G3 Plus Pack
Page 1: ...6F8C1590 Unified Controller nv Series G3 I O Adapter Module GA932 Instruction Manual ...
Page 46: ...Chapter 3 Setting 6F8C1590 34 ...
Page 50: ...Chapter 4 Startup and Shutdown 6F8C1590 38 38 ...
Page 51: ...39 Chapter 5 Troubleshooting This chapter describes troubleshooting for GA932 module ...
Page 64: ...Chapter 6 Maintenance and Inspection 6F8C1590 52 ...
Page 75: ...63 Appendix B Outside Dimensions ...
Page 77: ...65 Appendix C Related Products ...
Page 80: ...1590 1 1704 ...