Chapter 1 Introducing GA932 Module
6F8C1590
2
1.1 Functions and Characteristics of GA932 Module
G3 I/O adapter module GA932 is a module to connect PROSEC T series T3/T3H
I/O module (G3 I/O) to the Unified Controller nv series type 1 light controller.
GA932 module allows you to replace the existing PROSEC T series T3/T3H I/O
module (G3 I/O) to Unified Controller nv series type 1 light controller. One
GA932 module can be used per PUM12 and up to 76 modules (10 slots of basic
unit plus 11 slots x 6 units of expansion unit) can register 4864 points G3 I/O
(when 64 points DI/DO module is used).(However, a mixed configuration of
GA932 and SA912+SA931 can not be used, and only one can be used for
either.)
The I/O variables of G3 I/O module and the network variables can be
registered 2Kw for input and 1Kw for output per GA932 module. These Input
and output data can be assigned to the high-/medium-speed blocks
(selectable) of TC-net I/O loop scan for each GA932, the data can be input
and output between PUM12 and G3 I/O module.
■
Characteristics of GA932 module
High-speed transmission
The I/O data transmission between GA932 module and PUM12 realizes to
speed up at transmission gate array.
High reliability
The I/O data between GA932 module and PUM12 is transmitted cyclically, a
temporally error correction is performed automatically.
Figure 1-1 Example of using GA932
GA932
GA922-1,GA922-2
:
G2 I/O adapter
SA912-1,SA912-2
:
TC-net I/O adapter
GA932
:
G3 I/O adapter
PUM12
Controller
High speed serial TC-net I/O Loop
G2 I/O
adapter
LP1
Node 14
Node: 3
Node 7
Node 8
Node 4
SA912-1
TC-net I/O
Module
G3 I/O
Module
GA922-2
GA922-1
G2-I/O
Module
LP2
G2-I/O
Module
TC-net
I/O adapter
LP2
SA912-2
TC-net I/O
Module
LP2
LP2
LP1
LP1
LP1
LP1
LP2
・
When there are up to
16 I / O modules under GA 922,
GA 922 uses the node number for one module.
・
When there are
16 or more I / O modules under GA 922,
GA 922 uses the node number for two modules.
Summary of Contents for G3 Plus Pack
Page 1: ...6F8C1590 Unified Controller nv Series G3 I O Adapter Module GA932 Instruction Manual ...
Page 46: ...Chapter 3 Setting 6F8C1590 34 ...
Page 50: ...Chapter 4 Startup and Shutdown 6F8C1590 38 38 ...
Page 51: ...39 Chapter 5 Troubleshooting This chapter describes troubleshooting for GA932 module ...
Page 64: ...Chapter 6 Maintenance and Inspection 6F8C1590 52 ...
Page 75: ...63 Appendix B Outside Dimensions ...
Page 77: ...65 Appendix C Related Products ...
Page 80: ...1590 1 1704 ...