2. Indoor unit line address manual setting/change
[For 30 or more refrigeration systems (when used together with the SMMS series, the number of
refrigeration systems of the SMMS series is included.)]
The line address change/setting procedure for up to the 29th refrigeration system is the same as that
described in step 1 on the previous page.
• Since all line addresses are set to
“1”
except for group control by the automatic address setup function
after system power-on, change the line addresses for each refrigeration system using the wired remote
controller.
• Also change the indoor addresses so that they are not duplicated.
NOTE
• For changing/setting line addresses using the wired remote controller, refer to
“Manual address setup
procedure”
.
• Line addresses must be unique for each refrigeration system. Set a line address that is different from
any of line addresses of other refrigeration systems.
(If indoor units of the SDI series are operated under central control together with those of the SMMS
series, set line addresses different from those of the SMMS series.)
1
1
0
30
1
0
1
1
0
30
2
0
1
1
1
30
3
1
2
1
2
2
1
2
Central
control device
Refrigeration
system 30
Refrigeration
system 31
Refrigeration
system 32
Refrigeration
system 33
Outdoor
Outdoor
Outdoor
Outdoor
Indoor
Indoor
Indoor
Indoor
Remote
controller
Remote
controller
Remote
controller
Line address
Indoor address
Group address
Line address
Indoor address
Group address
Example of addresses after
automatic address setup
After manual system change
34-EN