High-Wall Type
Installation Manual
– 39 –
Toshiba
F06
ALT
Outdoor unit temp.
sensor (TE/TS) error
Outdoor
Outdoor temp. sensors (TE/TS),
outdoor P.C. board --- Open-
circuit or short-circuit of the heat
exchanger temp. sensor was
detected.
Entire
stop
F07
ALT
TL sensor error
Outdoor
TL sensor may be displaced,
disconnected or short-circuited.
Entire
stop
F08
ALT
Outdoor unit outside
air temp. sensor error
Outdoor
Outdoor temp. sensor (TO),
outdoor P.C. board --- Open-
circuit or short-circuit of the
outdoor air temp. sensor was
detected.
Operatio
n
continue
d
F10
ALT
Indoor unit room
temp. sensor (TA)
error
Indoor
Room temp. sensor (TA), indoor
P.C. board --- Open-circuit or
short-circuit of the room temp.
sensor (TA) was detected.
Auto-
reset
F12
ALT
TS sensor error
Outdoor
TS sensor may be displaced,
disconnected or short-circuited.
Entire
stop
F13
ALT
Heat sink sensor
error
Outdoor
Abnormal temperature was
detected by the temp. sensor of
the IGBT heat sink.
Entire
stop
F15
ALT
Temp. sensor
connection error
Outdoor
Temp. sensor (TE/TS) may be
connected incorrectly.
Entire
stop
F29
SIM
Indoor unit, other
P.C. board error
Indoor
Indoor P.C. board --- EEPROM
error
Auto-
reset
F31
SIM
Outdoor unit P.C.
board
Outdoor
Outdoor P.C. board ---- In the
case of EEPROM error.
Entire
stop
H01
Outdoor unit
compressor
breakdown
Outdoor
Current detect circuit, power
voltage --- Minimum frequency
was reached in the current
releasing control or short-circuit
current (Idc) after direct
excitation was detected
Wiring error of compressor (open
phase)
Entire
stop
H02
Outdoor unit
compressor lock
Outdoor
Compressor circuit ---
Compressor lock was detected.
Wiring error of compressor (open
phase)
Entire
stop
H03
Outdoor unit current
detect circuit error
Outdoor
Current detect circuit, outdoor
unit P.C. board --- Abnormal
current was detected in AC-CT or
a phase loss was detected.
Entire
stop
H04
Case thermostat
operation
Outdoor
Malfunction of the case
thermostat
Entire
stop
H06
Outdoor unit low-
pressure system
error
Outdoor
Current, high-pressure switch
circuit, outdoor P.C. board --- Ps
pressure sensor error was
detected or low-pressure
protective operation was
activated.
Entire
stop
L03
SIM
Duplicated header
indoor units
Indoor
Indoor address setting error ---
There are two or more header
units in the group.
Entire
stop
L07
SIM
Group line in
individual indoor unit Indoor
Indoor address setting error ---
There is at least one group-
connected indoor unit among
individual indoor units.
Entire
stop
L08
SIM
Indoor group address
not set
Indoor
Indoor address setting error ---
Indoor address group has not
been set.
Entire
stop
L09
SIM
Indoor power level
not set
Indoor
Indoor power level has not been
set.
Entire
stop
39-EN