Open the valve fully
Open the valve of the outdoor unit fully. A 4 mm
hexagon wrench is required for opening the valve.
For details, refer to the Installation Manual attached
to the outdoor unit.
Gas leak check
Check with a leak detector or soap water whether
gas leaks or not, from the pipe connecting section
or cap of the valve.
REQUIREMENT
Use a leak detector manufactured exclusively for
HFC refrigerant (R410A, R134a, etc.).
Wireless remote control A-B
selection
Using 2 wireless remote controllers for the
respective air conditioners, when the 2 air
conditioners are closely installed.
Wireless remote controller B setup
1.
Press
button on the indoor unit to turn the air
conditioner ON.
2.
Point the wireless remote controller at the indoor unit.
3.
Push and hold
button on the wireless remote
controller by the tip of the pencil.
“00” will be shown on the display.
4.
Press
during pushing
. “B” will be shown on
the display and “00” will be disappear and the air
conditioner will turn OFF. The wireless remote
controller B is memorized.
NOTE
• Repeat above step to reset wireless remote
controller to be A.
• The wireless remote controllers do not display
“A”.
• The factory default of the wireless remote
controllers is “A”.
CHK
MODE
CHK
PRESET
FAN
"B" Display
"00" Display
16-EN