3 - 16 3 - 16
MELSEC-A
3 SPECIFICATION
(2) Remote register assignment for ver. 2 remote device station (ver. 2
compatible slave station) setting
Table 3.8 indicates the remote register assignment for ver. 2 remote device
station (ver. 2 compatible slave station) setting.
Table 3.8 Remote Register Assignment for Ver. 2 Remote Device Station
(Ver. 2 Compatible Slave Station) Setting
Communication direction
Address
Description
Default value
Reference section
RWwm+0
H
A/D conversion enable/prohibit specification
0
Section 3.6.2
RWwm+1
H
CH.1 to 4 input range setting
0
RWwm+2
H
CH.5 to 8 input range setting
0
Section 3.6.3
RWwm+3
H
Average processing specification
0
Section 3.6.4
RWwm+4
H
CH.1 average time, number of times setting
0
RWwm+5
H
CH.2 average time, number of times setting
0
RWwm+6
H
CH.3 average time, number of times setting
0
RWwm+7
H
CH.4 average time, number of times setting
0
RWwm+8
H
CH.5 average time, number of times setting
0
RWwm+9
H
CH.6 average time, number of times setting
0
RWwm+A
H
CH.7 average time, number of times setting
0
RWwm+B
H
CH.8 average time, number of times setting
0
Section 3.6.5
Master Remote
RWwm+C
H
to
RWwm+F
H
Reserved 0
——
RWrn+0
H
CH.1 digital output value
0
RWrn+1
H
CH.2 digital output value
0
RWrn+2v
CH.3 digital output value
0
RWrn+3
H
CH.4 digital output value
0
RWrn+4
H
CH.5 digital output value
0
RWrn+5
H
CH.6 digital output value
0
RWrn+6
H
CH.7 digital output value
0
RWrn+7
H
CH.8 digital output value
0
Section 3.6.6
RWrn+8
H
Error code
0
Section 3.6.7
Remote Master
RWrn+9
H
to
RWrn+F
H
Reserved 0
——
m, n: Address allocated to the master module by the station number setting.
POINT
Do not read or write data from or to the reserved area of the remote register. If data
is read or written, we cannot guarantee the functions of the AJ65VBTCU-
68ADVN/ADIN.