5 - 19 5 - 19
MELSEC-A
5 PROGRAMMING
(e)
Selection of procedure registration (part 2)
Make setting for the AJ65VBTCU-68ADVN.
Click Procedure registration of target station number "4".
(f) Setting of procedure registration (part 2)
Set the conditions and execution for the AJ65VBTCU-68ADVN.
When the initial data processing request flag (RX18) turns ON and Remote
device station initialization procedure registration (SB0D) is set, the
following data are registered to the AJ65VBTCU-68ADVN.
Procedure Execution Condition in AJ65VBTCU-68ADVN
Execution Data
A/D conversion enable/prohibit specification: Channel 1, 2: Enable
(RWw0 :0003
H
)
CH. 1 to CH. 4 input range setting : Channel 1: 0 to 5V
: Channel 2: User range setting 1
(RWw1: 31
H
)
Average processing specification : Channel 1: Sampling processing
: Channel 2: Average processing, number
of times averaging
(RWw3: 200
H
)
CH. 2 average time, number of times setting: Channel 2: 16 times
(RWw5: 10
H
)
Initial data processing completion flag (RY18) is turned ON.
Initial data processing request flag (RX18) turns ON
Initial data setting request flag (RY19) is turned ON.
Initial data processing request flag (RX18) turns OFF
Initial data processing completion flag (RY18) is turned OFF.
Initial data setting completion flag (RX19) turns ON
Initial data setting request flag (RY19) is turned OFF.
(g)
Setting result (part 2)
The following indicates the setting result of the AJ65VBTCU-68ADVN.
POINT
For the case where the remote device station initialization procedure registration
function is not used but a sequence program is used to make setting, refer to the
user's manual of the used master module.