4 - 7 4 - 7
MELSEC-A
4 SETUP AND PREPARATION BEFORE OPERATION
(2) Applicable combinations and setting concepts
The following table indicates usability according to the combinations of the
master modules, the mode setting and station information (station type) of the
GX Developer network parameters, and the mode select switch setting of the
module. Refer to the following table and make selection.
: Usable, : Unusable
Network Parameter Setting
Model Select Switch Setting of
AJ65VBTCU-68ADVN/ADIN
Master Module
Mode setting
Station information
(station type)
Ver. 1 remote device
station (Ver. 1 compatible
slave station)
Ver. 2 remote device
station (Ver. 2 compatible
slave station)
Remote net ver.
1 mode
Remote device
station
Concept A
Ver. 1 remote
device station
Remote net ver.
2 mode
Ver. 2 remote
device station
Ver. 1 remote
device station
QJ61BT11
AJ61BT11
A1SJ61BT11
AJ61QBT11
A1SJ61QBT11
Remote net
additional mode
Ver. 2 remote
device station
Remote net ver.
1 mode
Remote device
station
Concept B
Ver. 1 remote
device station
Concept C
Remote net ver.
2 mode
Ver. 2 remote
device station
Concept D
Ver. 1 remote
device station
Concept E
QJ61BT11N
Remote net
additional mode
Ver. 2 remote
device station
Concept F
Setting Concept
Outline
Concept A
Select this concept when system expansion is not necessary. Select this concept when
the module replaces the conventional one as a maintenance product.
Concept B
Select this concept when system expansion is not necessary. Select this concept when
the module replaces the conventional one as a maintenance product.
Concept C
Select this concept when configuring a new system. The ver. 1 compatible slave station
and ver. 2 compatible slave station can be mixed. The ver. 1 remote device station
occupies 3 stations.
Concept D
Select this concept when configuring a new system. The ver. 1 compatible slave station
and ver. 2 compatible slave station can be mixed. The ver. 2 remote device station
occupies 1 station, and can connect more devices. Refer to Chapter 5 Programming.
Concept E
This concept allows this module to be newly added to the existing system. When there is
a station number used as the ver. 2 remote device station in the existing system, set the
station number of the ver. 1 remote device station to be added before that station.
The ver. 1 remote device station occupies 3 stations.
Concept F
This concept allows this module to be newly added to the existing system.
Set the station number of the ver. 2 remote device station to be added after the station
numbers used in the existing system. The ver. 2 remote device station occupies 1 station,
and can connect more devices. Refer to Chapter 5 Programming.
POINT
For use in the remote net ver. 2 mode or remote net additional mode, the master
module of QJ61BT11N and the peripheral software package of GX Developer
Version 8.03D or later are required.
For more information on the applicable modules (CPU modules, network modules)
and applicable software packages, refer to the CC-Link System Master/Local
Module User's Manual (Details) QJ61BT11N.