3 - 4 3 - 4
MELSEC-A
3 SPECIFICATION
3.3.1 Voltage input characteristics of the AJ68VBTCU-68ADVN
The voltage input characteristic graph of the AJ65VBTCU-68ADVN is shown below.
3
2
1
4095
4000
2000
-2000
-4000
-4096
0
1
-15
-10
-5
0
5
10
15
Analog input voltage (V)
Analog input parcitcal value
-96
Digit
al o
ut
put
value
Number
Analog Input Range
Setting
Offset
Value
Gain
Value
Digital Output
Value*
Maximum
Resolution
1)
-10 to +10V
0V
10V
-4000 to +4000
2.5mV
2)
0 to 5V
0V
5V
1.25mV
3)
1 to 5V
1V
5V
0 to 4000
1.0mV
—
User range setting 1
(-10 to +10V)
0V
10V
-4000 to +4000
2.5mV
—
User range setting 2
(0 to 5V)
0V
5V
0 to 4000
1.0mV
Fig. 3.1 Voltage Input Characteristic of the AJ65VBTCU-68ADVN
POINT
(1) Do not input more than ±15V. The element may be damaged.
(2) If the analog input provided corresponds to the digital output value* beyond its
range, the digital output value is fixed to the maximum or minimum.
For 0 to 4000, the digital output value is within the range -96 to 4095.
For -4000 to +4000, the digital output value is within the range -4096 to +4095.
(3) Within the analog input and digital output scopes of each input range, the
maximum resolution and accuracy are within the performance specification
range. Outside those scopes, however, they may not fall within the performance
specification range. (Avoid using the dotted line part in Fig. 3.1.)
(4) Set the offset and gain values of the user range setting within the range
satisfying the following conditions.
(a) Setting range when user range setting 1 is selected: -10 to +10V
(b) Setting range when user range setting 2 is selected: 0 to 5V
(c) (Gain value) > (Offset value)
If you attempt to make setting outside the setting range of (a) or (b), the "RUN"
LED flickers at 0.5s intervals.
Set the values within the setting range.
If you attempt to make setting outside the setting range of (c), the "RUN" LED
flickers at 0.5s intervals.
Make setting again.