73
I
ACTIVE
f the jumper wire is removed and the Sensor switch is in the
position, the controller will NOT operate automatically.
1. Re
3. Refer to the rain sensor user guide for set up and operating details.
Note:
Manual watering operation is not affected by operation of
the Rain Sensor.
4. Place the Sensor Bypass switch in the
Active
position.
When the Rain Sensor is active, all current and scheduled automatic
controller operation will placed on hold and the following message
will be displayed (example):
When the Rain Sensor hold is released, the controller will resume
automatic operation. The Sensor switch can be placed in the
Bypass
position at any time to ignore Rain Sensor operation.
move the wiring access hole plug from the bottom of the cabinet
and insert in the sensor connection cable.
2. R
Brown and White wires to the sensor terminals and the Red wires
to the 24 VAC terninals.
emove the jumper wire from the Sensor terminals. Connect the
Connecting a Rain Sensor
!
The sensor circuit is designed for a Normally Closed rain sensor.
If a rain sensor is NOT connected, the Sensor switch MUST be in
the “Bypass” position OR a jumper wire connected across the
sensor connection terminals.
Important:
Aug 08 2007 10:58:42am
RainSwitch M:
Jumper Wire
TWRS/TWRFS
Toro Rain Sensor
Red
Red
Brown
24V
AC
SENSOR
SENSOR
White